EasyManuals Logo

Hitachi RAS-3WHVRP Technical Catalogue

Hitachi RAS-3WHVRP
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
2 General data
Cooling mode application (EN 14825) (Models with cooling kit accessory)
TCGB0123 rev.2 - 10/2019
36
Model
Outdoor unit RAS-2WHVRP RAS-2.5WHVRP RAS-3WHVRP
Indoor unit
RWD-2.0NRWSE-
260S(-W)
RWD-2.5NRWSE-
260S(-W)
RWD-3.0NRWSE-
260S(-W)
Electrical power input in stand-by mode cooling
mode (Psb)
W 11.9 11.9 11.9
Electrical power input in thermostat-OFF cooling
mode (Pto)
W 0 0 0
Electrical power input in OFF mode (Poff) W 11.9 11.9 11.9
Electrical power input in crankcase heater in
cooling mode (Pck)
W 0 0 0
Sound power level of indoor unit (LWA) dB(A) 37 37 37
Sound power level of outdoor unit (LWA) dB(A) 61 63 64
Capacity control mode - Variable (Inverter) Variable (Inverter) Variable (Inverter)
Nominaloutdoorairow m
3
/h 2436 2436 2682
Model
Outdoor unit RAS-2WHVRP RAS-2.5WHVRP RAS-3WHVRP
Indoor unit
RWD-2.0NRWE-
200S-K
RWD-2.5NRWE-
200S-K
RWD-3.0NRWE-
200S-K
Electrical power input in stand-by mode cooling
mode (Psb)
W 11.9 11.9 11.9
Electrical power input in thermostat-OFF cooling
mode (Pto)
W 0 0 0
Electrical power input in OFF mode (Poff) W 11.9 11.9 11.9
Electrical power input in crankcase heater in
cooling mode (Pck)
W 0 0 0
Sound power level of indoor unit (LWA) dB(A) 37 37 37
Sound power level of outdoor unit (LWA) dB(A) 61 63 64
Capacity control mode - Variable (Inverter) Variable (Inverter) Variable (Inverter)
Nominaloutdoorairow m
3
/h 2436 2436 2682
Model
Outdoor unit RAS-2WHVRP RAS-2.5WHVRP RAS-3WHVRP
Indoor unit
RWD-2.0NRWE-
260S-K
RWD-2.5NRWE-
260S-K
RWD-3.0NRWE-
260S-K
Electrical power input in stand-by mode cooling
mode (Psb)
W 11.9 11.9 11.9
Electrical power input in thermostat-OFF cooling
mode (Pto)
W 0 0 0
Electrical power input in OFF mode (Poff) W 11.9 11.9 11.9
Electrical power input in crankcase heater in
cooling mode (Pck)
W 0 0 0
Sound power level of indoor unit (LWA) dB(A) 37 37 37
Sound power level of outdoor unit (LWA) dB(A) 61 63 64
Capacity control mode - Variable (Inverter) Variable (Inverter) Variable (Inverter)
Nominaloutdoorairow m
3
/h 2436 2436 2682

Table of Contents

Other manuals for Hitachi RAS-3WHVRP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RAS-3WHVRP and is the answer not in the manual?

Hitachi RAS-3WHVRP Specifications

General IconGeneral
BrandHitachi
ModelRAS-3WHVRP
CategoryHeat Pump
LanguageEnglish

Related product manuals