– 5 –
above 50mm
above 100mm
about 400mm
above 300mm
must not bend
above 100mm
2,300mm or more
1
2
Maximum pipe length 20m
Minimum pipe length 5m
above 200mm
above 700mm
above 200mm
above 50mm when
installed on the
ceiling of balcony
(
)
above 100mm
above 100mm
give clearance as
wide as possible
Plug
The Length of Indoor Unit
Connecting Cord
Figure showing the Installation of Indoor and Outdoor Unit.
Direction of Piping
There are 4 directions allowed,
namely, horizontally perpendicular
to the unit, vertically down from
right, horizontally out from right and
horizontally out to left.
Don’t form the piping downward
at the left of the unit.
● The difference in height
between the indoor and
outdoor unit should be
kept max 10m.
● The connecting pipe, no
matter big or small, should
all be insulated with
insulation pipe and then
wrapped with vinyl tape.
(The insulator will
deteriorate if it is not
wrapped with tape).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commersial
products).
inner diameter ø 16mm
Be sure to
completely
seal any
gap with
putty.
0.9m
1.6m
Connection
Horizontally
perpendicular
to the unit
!
CAUTION
•
The installation height of indoor unit must be 2.3m or more.