8. Safety and Control Device Setting
• Compressor Protection
High Pressure Switch: This switch cuts out the
operation of the compressor when the
discharge pressure exceeds the setting.
• Fan Motor Protection
When the thermistor temperature is reached to
the setting, motor output is decreased.
The other way, when the temperature becomes
lower, limitation is cancelled.
Model RAS-8FSNM(Q) RAS-10FSNM(Q) RAS-12FSNM(Q)
For Compressor
Pressure Switch Automatic Reset, Non-Adjustable
High Cut-Out MPa -0.05 -0.05 -0.05
-0.15 -0.15 -0.15
Cut-In MPa 3.2
+0.15 3.2+0.15 3.2+0.15
Fuse
3 , 380/415V, 50Hz
A 40 40 40
3 , 380V, 60Hz
A 40 40 40
3 , 220V, 60Hz
A 60 60 60
CCP Timer Non-Adjustable
Setting Time min. 3 3 3
For Condenser Fan Motor Automatic Reset, Non-Adjustable
Internal Thermostat (each one for each motor)
DC Cut-Out
o
C
120
+5 120+5 120+5
AC Cut-Out
o
C
135
+5 135+5 135+5
Cut-In
o
C
110 60
For Control Circuit
Fuse Capacity on PCB1, 5 A 5 5 5
Fuse Capacity on PCB3 A 10 10 10