11 Maintenance notes
Econofresh kit
SMGB0099 rev.0 - 12/2016
365
11
11.4  Econofresh kit
! DANGER
Wear gloves to avoid injuries when handling components.
! CAUTION
•  Clean the air lter more than once a year.
•  Clean the heat exchanger unit once or more every two years.
Turn off the power supply switches before starting maintenance work and t the appropriate safety locks and warnings.
Wait 5 minutes after turning off the power supply switches.
Clean the exchanger and/or air lter.
! CAUTION
•  Do not start the system without the air lter.
•  Turn on the power supply after completing the maintenance work.
11.5  Collection of refrigerant to replace the indoor unit
 
Collection of refrigerant after replacing the indoor unit
1  Connect the gauge manifold to the gas and liquid stop valve.
2  Switch the power supply ON.
3  Enable pin 1 of DSW1 on the outdoor unit PCB for cooling 
operation. Close the liquid stop valve and collect the refrigerant.
4  Carry out the following procedures immediately when the side 
pressure drops and the gas stop valve indicates –0.01 MPa.
? NOTE
Prevent the pressure from dropping below –0.01 MPa. If the pressure is 
less, the compressor may be faulty.
a.  Close the gas stop valve.
b.  Disable pin 1 of DSW1.
5  Switch off the power supply.
Gas stop valve
Liquid 
stop valve
Manifold gauge
DIP switch 
(DSW1-1 ON)