4 Electrical and control settings
Unit electrical wiring and connection
SMGB0099 rev.0 - 12/2016
149
4
RPK-(0.6-1.5)FSN(H)3M terminal board connections
Nº Part
1 Screw for earth wiring connection
2 Terminal board for power source
3 Terminal board for remote control switch cable
4 Fix the wires by cord clamp
5 Wire for receiver kit
6 Electrical box cover
2
3
4
6
RPK-(2.0-4.0)FSN3M terminal board connections
Nº Part
1 Terminal board for power source
2 Terminal board for remote control switch cable
3 Screw for earth wiring connection
4 Wire for receiver kit
5 Electrical box cover
6 Switch cover
2
3
5
6
Test runs
! CAUTION
• Be careful during the test runs, as some of the safety functions remain disabled: the units operate for two hours without switching off
via the thermostat. The three-minute compressor protection is not enabled during the test.
• Secure the rubber bushes to the panel using adhesive when the outdoor unit ducts are not used.
• The compressor remains at a standstill during forced stoppage.