6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
223
6
F6 – Automatic reset temperature for heating
This function is used to set automatic temperature reset in HEAT mode.
Setting condition Setting temperature for automatic reset
17 17ºC
18 18ºC
·
·
·
·
·
·
21 21ºC (Factory setting)
·
·
·
·
·
·
29 29ºC
30 30ºC
F7 – Operation stoppage prevention by remote control switch operational error
? NOTE
Operation is stopped by pressing the run/stop switch for 3 seconds.
F8 – Lock function for operation mode selection
This function is used to prevent changes to the operating mode.
F9 – Lock function for temperature setting
This function is used to prevent changes to the temperature setting.
FA – Lock function for fan speed selection
This function is used to prevent changes to the fan speed.
Fb – Lock function for swing louver operation
This function is used to prevent changes to automatic louver operations.
FC – Cooling lower limit for setting temperature
This function is useful to set the temperature range in cooling mode. It enables the cooling range to be reduced for
conguration using the remote control.
An example is shown in the following gure:
Temperature range at cooling
(standard)
Min at cooling +1ºC
Min at cooling +10ºC
Possible to set temperature
by remote controller switch
Impossible to set temperature
by remote controller switch
Fd – Heating upper limit for setting temperature
This function is used to dene an upper temperature setting limit for the HEAT function. This function enables the heating
range to be reduced for conguration using the remote control.
An example is shown in the following gure:
Temperature range at heating
(standard)
Min at heating -1ºC
Min at heating -10ºC
Possible to set temperature
by remote controller switch
Impossible to set temperature
by remote controller switch
FE – Not available