10  Servicing
356
SMGB0077 rev.0 - 01/2013
Remove the screws -A- securing the drain pan and remove it.
N O T E
Whentting,sealthedrainhosegasketcorrectly.
 
10.7.6  Fan removal
Remove  all  screws  -A-  from  the  lower  cover  of  the  unit  and 
separate it.
Remove  the  electrical  box  cover  Removal  of  the  electrical  box 
cover.
Disconnect the fan motor.
N O T E
To disconnect and remove the fan motor, previously see the 
chapter corresponding to the wiring diagrams in this Manual.
 
Remove the drain pan Removal of the drain pan.
Remove the wiring A- from the electrical box and release it from 
the support -B-.
Remove the screws -C- on both sides of the fan.
C A U T I O N
•  Make sure the fan can be removed correctly, without the 
risk of injuring anyone in the surrounding area.
•  The fan is heavy. Request the assistance of two operators 
to hold the fan while it is being removed.
 
Remove the screws -A- on both sides of the fan and remove the 
unit.
When tting, connect the fan motor connector to the electrical box 
in line with the previous conguration:
•  Connector CN24 LSP (Low Static Pressure); (factory-supplied).
•  Connector CN25 HSP (High Static Pressure).
N O T E
Service  cover  fan  assembly  parts  (runner,  fan  casing,  fan 
motor) must  be performed  once the fan  assembly has  been 
removed from the unit.