42
A10762300A-rev.1
4)Press“ ”tochangethescreenuntil
indicatingthecheckscreen“q1”.
5)Performthemotiondetection(wavinga
hand,etc)underthemotionsensorof
theindoorunitselectedwithforapprox.
10to15seconds.
6)Checkthevalueof“q1”after30*
1
secondsfromstartingthemotion
detectionatitem5).Thedetecting
informationofthemotionsensoragainst
themotiondetectionisindicatedwith
therangeof0%to100%.
*1: Thetransmissionbetweentheindoorunit
andthewiredcontrolleris30seconds
cycle.Thetimingofthemotiondetection
andthedetectedinformationdisplayis
showninthegurebelow.
NOTE:
Referto“OperationManual”ofindoorunit
forthesettingmethodofmotionsensor.
(“MotionSensorSetting”,“IfAbsent”and
“CheckInterval”canbeset.)
7)Checkthatthevalueof“q1”isneither
0%nor100%.
Ifthevalueisindicated0%or100%,
reperformtheprocedurefromitem5).
Ifthesamevalueisindicatedagain,
itmaybeamalfunctionofthemotion
sensor.
8)Press“Back/Help”andreturntothe
display.
(d) Thetemperaturedetectionsbythe
thermistorsareinvalidthoughthe
protectiondevicesarevalidduringthetest
run.
(e) SETFREESeries:
Accordingtothelabel“Checkingof
OutdoorUnitby7-SegmentDisplayon
PCB1”attachedtotherearsideofthe
frontcoveroftheoutdoorunit,check
temperature,pressureandtheoperation
frequency,andconnectedindoorunit
numbersby7-segmentdisplays.
(f) Tonishthetestrun,press“
On/O󰀨”
againorpassoverthesettestruntime.
Whenchangingthetestruntime,press
”or“ ”toselect“TestTime”.Then,set
thetestruntime(30to600minutes)by
pressing“ ”or“ ”.
30 sec.
Motion Detection Detected Information
Display
(for 30 seconds)
: Transmitting Cycle
30 seconds
30 sec.
Adj.Sel. OFF
Test Run: 2 units
MODE
SPEED
AUTO
COOL
LOUV.
Test Time 120min
Inverter 60Hz