P5416543 
17
Do not apply 
the refrigerant 
oil to the 
outside of the 
aring part.
(3)  Use specic are nut.
(4)  Check that there are no scratch, chip, 
deformation, gap or at the aring part.
(5)  Apply the refrigerant oil in a thin layer to the 
inside of the aring part of the pipe before 
tightening the are nut.  And the are nut 
must be tightened using two spanners 
according to the tightening torque as shown 
in the gure below.  The tightening work will 
be easier if tightening the are pipe in order 
of the liquid pipe, the gas pipe. 
Check the leakage of the refrigerant after the 
tightening work.
    *  If the refrigerant oil attaches to the air panel, 
it may cause a crack.  Pay attention not to 
attach.
NOTE:
Refrigerant oil is eld-supplied.
[ Ethereal Oil FVC50K, FVC68D 
  (Idemitsu Kousan Co. Ltd.) ]
Fig. 5.1  Tightening Work of Flare Nut
Required Tightening Torque  (JIS B8607)
Pipe Size Tightening Torque
f
6.35 mm (1/4) 14 - 18 (N-m)
f
9.52 mm (3/8) 34 - 42 (N-m)
f
12.7 mm (1/2) 49 - 61 (N-m)
f
15.88 mm (5/8) 68 - 82 (N-m)
Tighten the are nuts according to the 
specied torque.  If not, it may cause the 
refrigerant leakage.
mm (in.)
Diameter
(
f
d)
A
+0
-0.4
6.35 (1/4) 9.1
9.52 (3/8) 13.2
12.7 (1/2) 16.6
15.88 (5/8) 19.7
(2)  Perform the aring work as shown below.
5.2.2  Piping Connection
(1)  Open the air inlet grille and perform the 
connecting work from lower side.
(a)  Press and slide the cover of the air inlet 
grille in the direction of the arrow with 
ngers in the holes on the cover.
(b)  Remove the supporting string from the 
side plate.
(c)  While the air inlet grille is being opened, 
depress the knobs of hinge (
1
), push the 
air inlet grille toward arrow direction (
2
) 
and remove the air inlet grille.
fA
fd
90
o 
+
 2
o
45
o
 
+
 2
o
Holes
(2 or 3 Portions
Side Plate
Hinge
Depress the knob of
hinge and push the ai
inlet grille forward.
Depress
Push
1
2