42
P5416543
4) Press “ ” to change the screen until
indicating the check screen “q1”.
5) Perform the motion detection (waving a
hand, etc) under the motion sensor of
the indoor unit selected with for approx.
10 to 15 seconds.
6) Check the value of “q1” after 30*
1
seconds from starting the motion
detection at item 5). The detecting
information of the motion sensor against
the motion detection is indicated with
the range of 0% to 100%.
*1: The transmission between the indoor
unit and the remote control switch is 30
seconds cycle. The timing of the motion
detection and the detected information
display is shown in the gure below.
2) Select “Check 1” at the check menu
and press “OK”. (screen “B” will be
displayed.)
(This screen is NOT displayed when the
number of indoor unit connected with
the remote control switch is 1(one). In
this case, screen “C” will be displayed.)
3) Select the indoor unit by pressing
” and press “OK”. The check
data screen “C” will be displayed.
“B”
“C”
NOTE:
Refer to “Operation Manual” (P5415110)
of indoor unit for the setting method of
motion sensor. (“Motion Sensor Setting”,
“If Absent” and “Check Interval” can be
set.)
7) Check that the value of “q1” is neither
0% nor 100%.
If the value is indicated 0% or 100%,
reperform the procedure from item 5).
If the same value is indicated again,
it may be a malfunction of the motion
sensor.
8) Press “ ” (return) and return to the
display.
(e) The temperature detections by the
thermistors are invalid though the
protection devices are valid during the test
run.
(f) SET-FREE Series:
According to the label “Checking of
Outdoor Unit by 7-Segment Display on
PCB1” attached to the rear side of the
front cover of the outdoor unit, check
temperature, pressure and the operation
frequency, and connected indoor unit
numbers by 7-segment displays.
(g) To nish the test run, press “ ” (run/stop)
again or pass over the set test run time.
When changing the test run time, press
” or “ ” to select “T-RUN TIME”. Then,
set the test run time (30 to 600 minutes)
by pressing “ ” or “ ”.
Check 1
01-01 02-01 03-01 04-01
04-02
04-03
04-04
03-02
03-03
03-04
01-02 02-02
02-03
02-04
01-03
01-04
RTN.SEL.
OK
ENT.
Check 1:01-03
01
/
07
RTN.Next Page
q1 50
P2 10
P1 00
L4 00
Item Value
L3 00
30 sec.
Motion Detection Detected Information
Display
(for 30 seconds)
: Transmitting Cycle
30 seconds
30 sec.
Test Run: 2 units
MODE
SPEED
MED
COOL
LOUV.
SEL. ADJ
T-RUN TIME
510MIN
STOP