FEATURES
1-34
TCI-20007-rev.1
One indoor unit can be controlled by two optional
wired controllers separately mounted on the wall.
Indoor Unit Quantity: 1
Wired Controller Quantity: 2
Length of Wire Cable for Optional Wired Controller, Timer and Central Station
As the wired controllers, timer and central stations
do not include a controller cable, prepare one in
the eld, or use PRC-5K, 10K or 15K.
Use the twist pair cable (1P-0.75mm
2
) as
transmission wire cable for prevention of the
malfunction (The total cable length is max. 500m).
When the total cable length is within 30m, other
types of cable (more than 0.3mm
2
) can be used.
Indoor Unit Quantity: 1
Wired Controller Quantity: 1
Application Function of Wired Controller
One optional wired controller can start/stop up to
16 indoor units.
Indoor Unit Quantity: 16 (Maximum)
Wired Controller Quantity: 1