STANDARD SPECIFICATIONS
1-78 
TCI-20007-rev.1
12.  Standard Specications
OUTDOOR UNIT
CABINET - The cabinet shall be constructed of 
galvanized steel sheet, baked with synthetic resin 
paint.  The service panel shall be easily removable for 
service access to the electrical components and the 
compressor section.
REFRIGERATION CYCLE - Each refrigeration cycle 
shall be equipped with a scroll compressor, a solenoid 
valve, a heat exchanger, a 4-Way valve and are 
connection parts.
COMPRESSOR PROTECTION - The compressor 
shall be protected against breakdown by a quick 
response overcurrent relay, a high pressure switch, 
a wrap-around type oil heater and a discharge gas 
thermistor.
OUTDOOR FAN AND FAN MOTOR - The outdoor 
fan(s) shall be the plastic propeller type, dynamically 
balanced, and the fan shall be directly driven by a 
 W motor for horizontal-ow air discharge.  The 
fan motor shall be permanently lubricated and be 
protected from ingress of water.
OUTDOOR HEAT EXCHANGER - The heat 
exchanger shall be the multi-pass, cross-nned tube 
type, equipped with highly-ecient aluminum ns, 
mechanically bonded to oxygen-free copper tubes.  
The coil shall be cleaned, dehydrated and tested for 
leakage at the factory.
CONTROL - All electrical control devices, shall be 
enclosed in the indoor and outdoor units.
In addition to the compressor protection devices, the 
indoor fan motor shall be equipped with an internal 
thermostat.  The outdoor fan motor shall be protected 
by an internal thermostat.  The indoor fan motor shall 
be directly supplied with the power source from the 
control circuit.  The functions of these control devices 
shall compose an electrical sequence of manual 
starting and stopping, automatic continuous operation 
whenever the room thermostat requires, and the 
protection devices allow the operation.
CABINET - The cabinet shall be constructed of 
galvanized steel sheet.
REFRIGERATION CYCLE - The refrigeration cycle 
shall be equipped with solenoid valves and are 
connections to changeover the cycle in mediating 
between outdoor unit and indoor unit.
UNIT - The unit shall be a multi-split system inverter-
driven heat pump air conditioner for application with 
R410A or R32 refrigerants, and shall be composed of 
ceiling type indoor units and an outdoor unit, with a 
distributed refrigeration cycle, electrical components 
and enclosing cabinets.  Optional accessories shall 
also be provided upon customer request.  The indoor 
unit shall be constructed for installation, and the 
outdoor unit shall be completely weather-proofed for 
outdoor installation.  Both indoor unit and the outdoor 
unit shall be properly assembled, internally piped and 
wired, throughly tested, and charged with R410A or 
R32 refrigerant at the factory and shall comply with 
Japanese Industrial Standards and other Japanese 
standardization statues.
CAPACITY - The total capacity of the multi-split 
system inverter-driven heat pump air conditioner 
shall be          kW or greater with          
o
C air inlet dry 
bulb,          
o
C air inlet wet bulb,          
o
C outdoor air 
inlet temperature and          m
3
/min. indoor air ow.  
The total compressor power inputs shall not exceed 
         kW.  The total heating capacity of the split-type 
air conditioners shall be          kW or greater, with 
 
o
C indoor heat exchanger air inlet dry bulb, 
 
o
C outdoor heat exchanger air inlet dry bulb, 
 
o
C outdoor heat exchanger air inlet wet bulb, 
and          m
3
/min. indoor air ow.
The total compressor power input shall not exceed 
 kW.
INDOOR UNIT
CABINET - The cabinet shall be constructed of 
galvanized steel sheet or nished steel sheet, baked 
with synthetic resin-paint, with a plastic air panel 
assembly for cassette type unit, and be constructed of 
galvanized steel sheet for the in-the-ceiling duct type 
unit.
REFRIGERATION CYCLE - The refrigeration 
cycle shall be equipped with a heat exchanger, an 
electronic expansion valve, solenoid valves and are 
connections.
INDOOR FAN AND FAN MOTOR - The indoor fan 
shall be the multi-blade centrifugal type, statically 
and dynamically balanced, and directly driven by 
a          W motor for model           and a          W motor 
for model          .  The fan motor bearing shall be 
permanently lubricated.  The fan shall deliver 
         m
3
/min. air ow for model           and 
         m
3
/min. for model           at the nominal air ow.  
Three operating positions Hi, Me and Lo can be 
selected according to the required conditions.
INDOOR HEAT EXCHANGER - The heat exchanger 
shall be the multi-pass, cross-nned tube type, 
equipped with highly-ecient aluminum ns, 
mechanically bonded to seamless, oxygen-free 
copper tubes.  The ns shall be spaced at no more 
than 12 ns per 25.4mm.  The face area shall not be 
less than          m
2
 for model           and 
         m
2
 for model          .  The coil shall be cleaned, 
dehydrated and tested for leakage at the factory.