4-31
Chapter 4
For parameter configuration
[CA-01] to [CA-31]
Parameter mode (C code)
Intelligent input terminals setting
Code/Name
Range (unit)
Initial
value
CA-01 Input terminal [1] function
Reference
<Input
terminal
function list>
103 [PLA] Pulse
train input A is
restricted to
[CA-10],
104 [PLB] Pulse
train input B is
restricted to
[CA-11],
028(RS)
CA-02 Input terminal [2] function
015(SCHG)
CA-03 Input terminal [3] function
029(JG)
CA-04 Input terminal [4] function
032(FRS)
CA-05 Input terminal [5] function
031(2CH)
CA-06 Input terminal [6] function
003(CF1)
CA-07 Input terminal [7] function
004(CF2)
CA-08 Input terminal [8] function
002(RV)
CA-09 Input terminal [9] function
001(FW)
CA-10 Input terminal [A] function
033(EXT)
CA-11 Input terminal [B] function
034(USP)
The functions for the input terminals 19,A,B are
assigned in [CA-01] to [CA-09],[CA-10],[CA-11].
Input terminal NO/NC setting
Code/Name
Range (unit)
Initial
value
CA-21 Input terminal [1] active state
00(Normally
Open: NO)/
01(Normally
Closed: NC)
00
CA-22 Input terminal [2] active state
00
CA-23 Input terminal [3] active state
00
CA-24 Input terminal [4] active state
00
CA-25 Input terminal [5] active state
00
CA-26 Input terminal [6] active state
00
CA-27 Input terminal [7] active state
00
CA-28 Input terminal [8] active state
00
CA-29 Input terminal [9] active state
00
CA-30 Input terminal [A] active state
00
CA-31 Input terminal [B] active state
00
NO/NC for the Intelligent input terminals 1 to 9,A,B are
assigned in [CA-21] to [CA-29],[CA-30],[CA-31].
However, in the case of [RS] assignment the NO/NC will
not apply, only NO will apply.
[CA-41] to [CA-55]
Input terminal chatter prevention
Code/Name
Range (unit)
Initial
value
CA-41 Input terminal [1] response time
0 to 400(ms)
2
CA-42 Input terminal [2] response time
2
CA-43 Input terminal [3] response time
2
CA-44 Input terminal [4] response time
2
CA-45 Input terminal [5] response time
2
CA-46 Input terminal [6] response time
2
CA-47 Input terminal [7] response time
2
CA-48 Input terminal [8] response time
2
CA-49 Input terminal [9] response time
2
CA-50 Input terminal [A] response time
2
CA-51 Input terminal [B] response time
2
Above parameters set the time to wait after the input
change has ended, and for the input to become stable
and responsive.
Time allowed in simultaneous terminal change
Code/Name
Range (unit)
Initial
value
CA-55 Multistage input
determination time
0 to 2000(ms)
0
Sets the dead time for multistage speed and position