For parameter configuration
[Input terminal function list]
P/PI control
mode selection
For drooping control, [PPI]
switches between PI control
(OFF) and P control (ON).
Changes between the PI gain 1
(OFF) and 2(ON) of the speed
control system.
[SON]’s ON executes the
Servo-Lock operation.
By turning ON this terminal
before operation, the rise of
torque is accelerated by applying
the exciting current in advance.
Permission of
torque control
[ATR]’s ON enables the torque
control.
[TBS]’s ON enables the torque
bias.
[ORT]’s ON execute the home
position return function in pulse
train position control.
Acceleration/
Deceleration(LA
D) cancellation
[LAC]’s ON forces Accel/Decel
time to 0.00s.
Clearance of
position
deviation
Clears the position deviation of
position control mode.
Pulse train
position
reference input
enable
In the pulse train position control,
if [STAT] is ON, the pulse train
input is enabled.
In pulse train position control,
when [PUP]/[PDN] is turned on,
"Position bias setting[AE-08]" is
added/subtracted to/from the
position reference.
Multistage
position
settings
selection 1
The position reference can be
selected by changing the pattern
of ON/OFF states.
Multistage
position
settings
selection 2
Multistage
position
settings
selection 3
Multistage
position
settings
selection 4
Limit signal of
homing
function
Used by the Zero-Return position
operations of the position
control.
Start signal of
homing
function
When this signal is ON, the
forward drive in absolute position
control mode is limited (The
torque limit value in the forward
direction is set to 10%).
When this signal is ON, reverse
drive in absolute position control
mode is limited (Torque limit
value in reverse direction is set to
10%).
Switches position control (OFF)
and speed control (ON).
*1) LAD :Lead to acceleration and deceleration
[Input terminal function list]
[PSET]’s ON sets the actual
position to the Pre-set position
[AE-62].
When these functions are
assigned, they become general
purpose input signals of the EzSQ
function.
[PCC]’s ON clears the count for
the pulse counter function.
[ECOM]’s ON activates EzCOM.
[PRG]’s ON executes EzSQ.
Acceleration/
Deceleration
disable
[HLD]’s ON temporarily stops
Accel/Decel operation.
Run command is not possible
when the input terminal function
[REN] is assigned and it is OFF.
[DISP]’s ON locks the keypad
screen.
For pulse train input use.
For pulse train input use.
Emergency-forc
e drive
activation
Forces the set operation in
emergency state.
Regarding the braking control,
check signal for the contactor.
[DTR]’s ON starts data trace
function.
Z phase pulse input of the
external encoder. It is invalid
when using P1-FB.
[TCH]’s ON starts teach-in
function.