7-29
Chapter 7
Wire Connection and Optional Devices
Input terminals
All COM terminals are at the same potential.
When connecting a power supply between 1-9, A,
B and COM, switch SW5 to the external power
supply (EX).
You can switch between the sink/source logic of
input terminals by using SW6.
(Wiring example)
[ ] indicates the factory default setting.
Initial terminal function
[RS] Reset
Resets when trip occurs.
[SCHG] Switch of frequency command
Switches between the main speed command
[AA111](OFF) and auxiliary speed command
[AA112](ON).
[JG] Jogging
When operation command is input with [JG]ON,
operation is performed at the frequency set for
[AG-22].
[FRS] Free-run stop
The motor performs free-run when [FRS] is ON.
[2CH] 2-stage acceleration/deceleration
When [2CH] is ON, the acceleration/deceleration
time 2[AC124]and [AC126] are enabled.
[EXT] External trip
When [EXT] is ON, trip [E012] is issued.
[FW] normal rotation and [RV] reverse rotation
Normal
rotation
FW
Reverse
rotation
RV
Description
OFF OFF
There is no command.
ON
OFF
Forward rotation command operation
OFF
ON
Reverse rotation command operation
ON
ON
There is no command (logic inconsistency).
[CF1] multistage speed 1 and [CF2] multistage speed
2 commands
Multistage
speed 1
CF1
Multistage
speed 2
CF2
Description
OFF OFF
The set frequency command is enabled
ON
OFF
[Ab-11] frequency command is enabled
OFF
ON
[Ab-12] frequency command is enabled
ON
ON
[Ab-13] frequency command is enabled
*) By configuring CF3 and 4, you can configure up
to 15th speed.
[USP] Prevention of power restoration restarting
When [USP] is ON, upon power-on, trip [E013] is
issued if the operation command is issued.
Terminal
symbol
Terminal
name
Description
Electrical characteristics
Input terminal
Digital input
Contact
9, 8, 7,
6, 5, 4,
3, 2, 1
Input
terminal
You can select terminal functions using
the parameter settings corresponding to
each terminal. You can switch between
the sink logic and source logic by
switching SINK/SRC of SW6.
Voltage between each input/COM
ON voltage Min. DC18V
OFF voltage Max. DC3V
Maximum allowable voltage DC27V
Load current 5.6mA (at DC27V)
Contact/pulse
A Pulse
input-A
When [CA-90] is set to 00, A, and B
terminals can be used as input terminals.
You can select terminal functions using
the parameter settings corresponding to
each terminal.
When [CA-90] is not set to 00, they are
used as terminals for pulse string input.
The maximum input pulse is 32kpps.
Voltage between each input/COM
ON voltage Min. DC18V
OFF voltage Max. DC3V
Maximum allowable voltage DC27V
Load current 5.6mA (at DC27V)
Maximum 32kpps pulse input
B Pulse
input-B
Common
COM Common
for input
terminal
Common terminals for digital input
terminals (1,2,3,4,5,6,7,8,9,A,B).
There are
three COM terminals.
Input
1
[RS]
2
[SCHG]
3
[JG]
4
[FRS]
5
[2CH]
6
[CF1]
7
[CF2]
8
[RV]
9
[FW]
A
[EXT]
B
[USP]
COM
COM
COM
Control circuit terminal
area
SW6
SW5