Wire Connection and Optional Devices
Output terminals
(Wiring example)
AL:[AL] 16:[ZS]
○
X
: Devices such as lamp, relay, PLC
○
RY
: Relay
・[ ] indicates the factory default setting.
Initial terminal function
[RUN:001] During operation signal
・Turns ON during operation (PWM output).
[FA1:002] Frequency reached signal
・Turns ON when the output frequency reaches the
command frequency.
[FA2:003] Frequency reached signal 2
・Turns ON when the output frequency reaches the set
frequency [CE-10]-[CE-13].
[IRDY:007] Operation ready completion
・Turns ON when operation is ready.
[OL:035] Overload advance notice
・Turns ON when current exceeds the level of overload
advance notice.
[ZS:040] 0 Hz detection signal
・Turns ON when the output frequency goes below the
0-Hz detection value level [CE-33].
* Make sure to use diode. Otherwise, the internal
circuit may be damaged.
About [AL] operation
・When [CC-17] = 00
ON Normal Open Close
ON Trip Close Open
OFF – Open Close
・When [CC-17] = 01
ON Normal Close Open
ON Trip Open Close
OFF – Open Close
Electrical characteristics
15,14
13,12
11
Output
terminal
You can select terminal functions
using the parameter settings
corresponding to each terminal.
These terminals can be used both
in sink logic or source logic.
Open collector output
・Between each terminal and CM2
・Voltage drop at ON: 4V or below
・Maximum allowable voltage: 27V
・Maximum allowable current: 50mA
CM2
Common
for
output
terminal
Common terminals for output
terminals 11-15
Relay
16A
16C
1a relay
terminal
A relay for contact A output.
Maximum capacity of contact
・AC250V, 2A (resistance)/AC250V,
1A (induction)
Minimum capacity of contact
・DC1V ,1mA
AL0
AL1
AL2
1c relay
terminal
A relay for contact C output.
Maximum capacity of contact
AL1/AL0:
・AC250V, 2A (resistance)/AC250V,
0.2A (induction)
AL2/AL0:
・AC250V, 1A (resistance)/・AC250V,
0.2A (induction)
Minimum capacity of contact (common)
・AC100V, 10mA/DC5V ,100mA
16A
Alarm relay output
terminal
X
Control circuit terminal area