14
Code Function Name Setting Range
Setting During
Operation
(allowed or not)
Change During
Operation
(allowed or not)
Default
Setting
Operation mode and Accel. / Decel. function
A085 Operation mode selection 00 (normal operation), / 01 (energy-saving operation) × × 00
A086 Energy saving mode tuning 0.0 to 100.0 [%] 50.0
A092 Acceleration (2) time setting 0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s] 10.00
A292 Acceleration (2) time setting, 2nd motor 0.01 to 99.99 / 100.0 to 999.9 /1000. to 3600. [s] 10.00
A093 Deceleration (2) time setting 0.01 to 99.99 /100.0 to 999.9 / 1000. to 3600. [s] 10.00
A293 Deceleration (2) time setting, 2nd motor 0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s] 10.00
A094 Select method to switch to Acc2 / Dec2 prole
00 (switching by 2CH terminal) / 01 (switching by setting) /
02 (Forward and reverse)
× × 00
A294 Select method to switch to Acc2 / Dec2 prole, 2nd motor × × 00
A095 Acc1 to Acc2 frequency transition point 0.00 to 99.99 / 100.0 to 400.0 [Hz] × × 0.00
A295 Acc1 to Acc2 frequency transition point, 2nd motor 0.00 to 99.99 /100.0 to 400.0 [Hz] × × 0.00
A096 Dec1 to Dec2 frequency transition point 0.00 to 99.99 / 100.0 to 400.0 [Hz] × × 0.00
A296 Dec1 to Dec2 frequency transition point, 2nd motor 0.00 to 99.99 / 100.0 to 400.0 [Hz] × × 0.00
A097 Acceleration curve selection
00 (linear) / 01 (S curve) / 02 (U curve) / 03 (inverted-U curve) / 04 (EL-S curve)
× × 01
A098 Deceleration curve selection × × 01
External
frequency tuning
A101 [OI]-[L] input active range start frequency 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
A102 [OI]-[L] input active range end frequency 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
A103 [OI]-[L] input active range start current 0 to 100 [%] × 20
A104 [OI]-[L] input active range end voltage 0 to 100 [%] × 100
A105 [OI]-[L] input start frequency enable 00 (A101) / 01 (0Hz) × 00
Accel./
Decel. curve
A131 Acceleration curve constant setting (for S, U, Inverse U) 01 to 10 × 02
A132 Deceleration curve constant setting (for S, U, Inverse U) 01 to 10 × 02
Operation target
frequency
A141 A input select for calculate function
00 (digital operator) / 01 (keypad potentiometer) / 02 (input via O) / 03 (input via OI) /
04 (external communication) / 05 (option) / 07 (pulse train frequency input)
× 02
A142 B input select for calculate function × 03
A143 Calculation symbol 00 (A141 + A142) / 01 (A141 - A142) / 02 (A141 × A142) × 00
A145 ADD frequency 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
A146 ADD direction select 00 (frequency command + A145) / 01 (frequency command - A145) × 00
Acceleration
and deceleration
A150 Curvature of EL-S-curve at the start of acceleration 0 to 50 [%] × × 10
A151 Curvature of EL-S-curve at the end of acceleration 0 to 50 [%] × × 10
A152 Curvature of EL-S-curve at the start of deceleration 0 to 50 [%] × × 10
A153 Curvature of EL-S-curve at the end of deceleration 0 to 50 [%] × × 10
Others
A154 Deceleration stop frequency setting 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
A155 Deceleration stop time setting 0.0 to 60.0 [s] × 0.0
PID
control
A156 PID sleep function action threshold 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
A157 PID sleep function action delay time 0.0 to 25.5 [s] × 0.0
Frequency trimming
A161 [VR] input active range start frequency 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
A162 [VR] input active range end frequency 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
A163 [VR] input active range start current 0 to 100 [%] × 0
A164 [VR] input active range end voltage 0 to 100 [%] × 100
A165 [VR] input start frequency enable 00 (A161) / 01 (0Hz) × 01
Restart after instantaneous power failure
b001 Selection of automatic restart mode
00 (tripping) / 01 (starting with 0 Hz) / 02 (starting with matching frequency) /
03 (tripping after deceleration and stopping with matching frequency) /
04 (restarting with active matching frequency)
× 00
b002 Allowable under-voltage power failure time 0.3 to 25.0 [s] × 1.0
b003 Retry wait time before motor restart 0.3 to 100.0 [s] × 1.0
b004 Instantaneous power failure / under-voltage trip alarm enable 00 (disabled) / 01 (enabled) / 02 (disabled during stopping and decelerating to stop) × 00
b005
Number of restarts on power failure /
under-voltage trip events
00 (16 times) / 01 (unlimited) × 00
b007 Restart frequency threshold 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
b008 Selection of retry after tripping
00 (tripping) / 01 (starting with 0 Hz) / 02 (starting with matching frequency) /
03 (tripping after deceleration and stopping with matching frequency) /
04 (restarting with active matching frequency)
× 00
b010 Selection of retry count after undervoltage 1 to 3 [times] × 3
b011 Start freq. to be used in case of freq. matching restart 0.3 to 100.0 [s] × 1.0
Electronic Thermal
b012 Level of electronic thermal setting Set a level between 20% and 100% for the rated inverter current [A] ×
Rated current
of inverter
b212 Level of electronic thermal setting, 2nd motor Set a level between 20% and 100% for the rated inverter current [A] ×
Rated current
of inverter
b013 Electronic thermal characteristic
00 (reduced-torque characteristic) / 01 (constant-torque characteristic) /
02 (free setting)
× 01
b213 Electronic thermal characteristic, 2nd motor × 01
b015 Free setting, electronic thermal frequency (1) 0 to "electronic thermal frequency (2)" [Hz] × 0
b016 Free setting, electronic thermal current (1) Range is 0 to inverter rated current Amps [A] × 0.00
b0 17 Free setting, electronic thermal frequency (2) "electronic thermal frequency (1)" to "electronic thermal frequency (3)" [Hz] × 0
b018 Free setting, electronic thermal current (2) Range is 0 to inverter rated current Amps [A] × 0.00
b019 Free setting, electronic thermal frequency (3) "electronic thermal frequency (2)" to 400 [Hz] × 0
b020 Free setting, electronic thermal current (3) Range is 0 to inverter rated current Amps [A] × 0.00
Function List
[ = Allowed × = Not parmitted]
Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309