18
Function List
Code Function Name Setting Range
Setting During
Operation
(allowed or not)
Change During
Operation
(allowed or not)
Default
Setting
Levels and output terminal status
C038 Output mode of low load detection signal
00 (output during acceleration/deceleration and constant-speed operation) /
01 (output only during constant-speed operation)
× 01
C039 Low load detection level Set range: 0 to 200% of inverter rated current [A]
Rated current
of inverter
C040 Output mode of overload warning
00 (output during acceleration /deceleration and constant-speed operation) /
01 (output only during constant-speed operation)
× 01
C041 Overload level setting Set range: 0 to 200% of inverter rated current [A]
115% of
Rated current
C241 Overload level setting, 2nd motor Set range: 0 to 200% of inverter rated current [A]
115% of
Rated current
C042 Frequency arrival setting for acceleration 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
C043 Frequency arrival setting for deceleration 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
C044 PID deviation level setting 0.0 to 100.0 [%] × 3.0
C045 Frequency arrival signal for acceleration (2) 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
C046 Frequency arrival signal for deceleration (2) 0.00 to 99.99 / 100.0 to 400.0 [Hz] × 0.00
C047 Pulse train input scale conversion for EO output 0.01 to 99.99 1.00
C052 PID FBV function high limit 0.0 to 100.0 [%] × 100.0
C053 PID FBV function variable low limit 0.0 to 100.0 [%] × 0.0
C054 Over-torque/under-torque selection 00 (Over torque) / 01 (under torque) × 00
C055 Over / under-torque level (Forward powering mode) 0 to 200 [%] × 100
C056 Over / under-torque (Reverse regen. mode) 0 to 200 [%] × 100
C057 Over/ under-torque (Reverse powering mode) 0 to 200 [%] × 100
C058 Over / under-torque level (Forward regen. mode) 0 to 200 [%] × 100
C059 Signal output mode of Over / under torque
00 (output during acceleration /deceleration and constant-speed operation) /
01 (output only during constant-speed operation)
× 01
C061 Electronic thermal warning level setting 0 to 100 [%] × 90
C063 Zero speed detection level setting 0.00 to 99.99 / 100.0 [Hz] × 0.00
C064 Heat sink overheat warning 0. to 110. [
º
C] × 100
Communication function
C071 Communication speed selection
03 (2400bps) / 04 (4800bps) / 05 (9600bps) / 06 (19200bps) / 07 (38400bps) /
08 (57600bps) / 09 (76800bps) / 10 (115200bps)
× 05
C072 Node allocation 1 to 247 × 1
C074 Communication parity selection
00 (no parity) /
01 (even parity) /
02 (odd parity)
× 00
C075 Communication stop bit selection 1 (1bit) / 2 (2bit) × 1
C076 Communication error select
00 (tripping) /
01 (tripping after decelerating and stopping the motor) /
02 (ignoring errors) /
03 (stopping the motor after free-running) /
04 (decelerating and stopping the motor)
× 02
C077 Communication error time-out 0.00 to 99.99 [s] × 0.00
C078 Communication wait time 0 to 1000 [ms] × 0
Adjustment
C081 O input span calibration 0. to 200.0 [%] 100.0
C082 OI input span calibration 0. to 200.0 [%] 100.0
C085 Thermistor input (PTC) span calibration 0. to 200.0 [%] 100.0
C091 00 (Disable) / 01 (Enable) 00 00
Communication
function
C096 Communication selection
00 (Modbus-RTU) /
01 (EzCOM) /
02 (EzCOM [administrator])
× × 00
C098 EzCOM start adr. of master 01 to 08 × × 01
C099 EzCOM end adr. of master 01 to 08 × × 01
C100 EzCOM starting trigger
00 (Input terminal) /
01 (Always)
× × 00
Others
C101 UP / DWN memory mode selection
00 (not storing the frequency data) /
01 (storing the frequency data)
× 00
C102 Reset selection
00 (resetting the trip when RS is on) /
01 (resetting the trip when RS is off) /
02 (enabled resetting only upon tripping [resetting when RS is on]) /
03 (resetting only trip)
00
C103 Restart mode after reset
00 (starting with 0 Hz) / 01 (starting with matching frequency) /
02 (restarting with active matching frequency)
× 00
C104 UP / DWN clear: terminal input mode selection
00 (0Hz) /
01 (EEPROM data when power supply is turned on)
× 00
C105 EO gain adjustment 50 to 200 [%] 100
C106 AM gain adjustment 50 to 200 [%] 100
C109 AM bias adjustment 0 to 100 [%] 0
C111 Overload setting (2) Set range: 0 to 200% of inverter rated current [A]