Chapter 7 Description of Configure Parameters
Pn 01 Default display content:1——30000
RUN: 1 means it will display runtime frequency
Otherwise, it displays motor’s synchronization speed. 2
——
30000 is motor synchronization speed
STOP
:
it will display frequency given by external signal.
Pn 02 Initial startup frequency by panel or other method Range:
000.01Hz-400.00Hz,the initial panel data and
external signal frequency during startup.
Pn 03 Source of runtime frequency with range:1—7
1 Potentiometer 2 Panel button
3 External 0-5V signal 4 External 0-10V signal
5 External 0-20mA signal 6 External digital signal
7 Multi-segment signal
Pn 04 Source of runtime command with range
:
1—2
1 Panel button control 2 External signal control
Pn 05 clockwise / anticlockwise disable with range
:
1—3
1 clockwise enable only 2 anticlockwise enable only
3 clockwise / anticlockwise enable
Pn 06 Method to stop VFD with range:1—2
1 stop by itself 2 stop by deceleration
Pn 07 Start again by external signal with range
:
1—2
1 disable 2 enable
Description: when the power on the external operation of
the signal is allowed to start effectively.
Pn 08 Acceleration time with range:000.01S-650.00S
Accelerate time (from 0Hz to Pn10).