103
FireNET 4127 I & O Manual v1.90 UL
Section 8 - Advanced Front Panel Operations and Programming
(Access Level 3)
8.1 Access Level Overview
The FireNET 4127 has 3 modes of operation. Access Levels 1 and 2 are operational
levels that allow the user to perform operational commands such as silencing an alarm
or resetting the panel. Access Levels 1 and 2 are explained in further detail in Section 7
- Basic Front Panel Operation and Programming.
Access Level 3 is an installer level operating mode that allows the user to perform
some of the basic programming commands used to configure the FN-4127 fire alarm
system.
Some of the basic programming functions for the FireNET 4127 control panel can be
done from the front panel controls. To fully program the FireNET 4127 fire alarm system
however, you should use a PC running the Loop Explorer software package (See
Section 9).
This section covers the basic programming functions that can be done from the front
panel controls of the FN-4127 fire alarm control panel.
8.1.1 Entering Access Level 3
In order to enter Access Level 3 operating mode you must first enter Access Level 2
operating mode. From the Access Level 2 Main Menu you can select Access Level 3.
To enter into
Access Level 3 follow these steps:
1. Press any arrow key to enable the panel.
2. Using the arrow keys enter the 5 digit code for Access Level 2. You can only
use digit values of 1-4. The up/down arrow keys represent the values 1-4. Up
= 1, Right = 2, Down = 3, and Left = 4. The default Access Level 2 code is
22222
3. Press the Enter key. The front panel graphic display will confirm you are in
Access Level 2.
4. Press the right arrow key to access the Access Level 2 Main Menu.
5. Press the down arrow key until
Access Level 3 is highlighted with a
triangular arrow to the left of it.