A.3 Compatible Notification Appliances
The A.3 tables list notification appliances that have been verified and listed to be compatible
with the FireNET fire alarm control panel per UL864 9
th
Edition.
When
non-synchronized notification appliances are used on the NAC outputs, they are
rated as “
Special Application” by UL Laboratories. In this case specific device
compatibility is not required. For these types of notification appliances the Hochiki 10K end
of line resistor PN# 0400-01046 may be used in lieu of the end of line device PN# 0400-
01023 if desired.
When
synchronized notification appliances are used on the NAC outputs, they are rated as
“
Special Application” by UL Laboratories with a range of compatibility from 19.3 ~ 25.95
VDC. In this case specific device compatibility is required as outlined in the tables A.3.1-
A.3.3 below. For proper operation use polarized notification appliances with a Hochiki end
of line device PN# 0400-01023.
NOTE:
Synchronized audible notification appliances connected to one NAC output are not to be
installed within hearing range of the synchronized audible notification appliances on another
NAC circuit.
Synchronized visual notification appliances connected to one NAC output are not to be
installed within line of site of the synchronized visual notification appliances on another NAC
circuit.