FireNET 4127 I & O Manual 216 v1.90 UL
Appendix B – Panel Door Label Drawing
X2- SIDE TERMINAL STRIP ELECTRICAL RATINGS FOR MAIN CONTROL UNIT
24VDC
0VDC
0VDC
12VDC
12VDC
24VDC
24VDC
12VDC
500mA
500mA
30mA
500mA
100mA
100mA
500mA
500mA
100mA
100mA12VDC
SUPERVISED POLARITY REVERSING SIGNALING
OUTPUTS FOR FIRE, TROUBLE, PROGRAMMABLE
REMOTE CONTROL DIGITAL PULL-DOWN INPUTS
SIGNAL FOR ACTIVATING REMOTE INPUTS
RS485 TO I/O BOARDS
RS485 TO I/O BOARDS
AUXILIARY 24V SUPPLY
AUXILIARY 24V SUPPLY
RS485 TO OTHER PANELS
RS485 TO OTHER PANELS
NETWORK
IN/OUT
AUX
24V
COMMS
REMOTE/AUX
INPUTS
DC GROUND
VOLTAGE
OUTPUTS
+
-
0V
+
-
+
-
+
-
24VDC
HOCHIKI AMERICA CORPORATION
This Product shall be installed in
accordance with FireNET Installation
Manual: PN # 1700-09948
Version # 1.88
Issued: 07/02/2010
18 AWG 3900 Feet
16 AWG 6200 Feet
14 AWG 10,000 Feet
Class A Style 6 or 7 - For SLC Devices (Smoke / Heat Sensors and Modules)
Class B Style 4 - For SLC Devices (Smoke / Heat Sensors and Modules)
Total wire must not
exceed 10,000 feet
from the control
panel when using
#14 AWG
Conventional Relay Contacts rated for 1A @ 30VDC.
Must be connected to power limited source.
(Not supervised) (Resistive)
RS485 FROM PREVIOUS FireNET PANEL
ON NETWORK (Supervised)
DIGITAL INPUTS (EXAMPLE FOR INPUTS 1-8)
USE DRY CONTACTS ONLY
(Not Supervised)
RS485 TO I/O BOARDS (Supervised)
AUX 24VDC POWER TO I/O BOARDS 500 mA max.
(Supervised)
+
-
POLARITY
REVERSING
DEVICE
500 mA @24VDC
max.
EXAMPLE OF FIRE ROUTING, TROUBLE
ROUTING, & PROGRAMMABLE OUTPUT
1N4004S END-OF-LINE DIODE (EOLD) P/N 0400-01024
(Supervised)
10K OHM END-OF-LINE RESISTOR (EOLR) P/N 0400-01046
(Supervised)
SLC INITIATING DEVICES
+
-
+
-
Class B Style Y - For Indicating Devices
NOT
USED
FireNET WIRING DIAGRAM
P/N 1700-04345 DATE 07/02/2010
AGENCY LISTINGS AND REQUIREMENTS
Install in accordance with NFPA 70, 72 and 13.
The FireNET 4127 is suitable as follows
:
- Commercial Protected- Premises Control Unit
for Local signaling. Install Indoors only
in a dry
environment.
- Types of signaling services are automatic,
manual, waterflow, & sprinkler supervisory.
- Style 4, 6, or 7 for Signaling Line Circuits
- Style Y for Notification Appliance Circuits
- Non-coded signaling
- Central Station Service (DACT)
- Remote Station Service (DACT)
- UL Releasing Function for Pre-Action with use
of SOM-R Module
THIS UNIT INCLUDES AN
OPTIONAL ALARM
VERIFICATION FEATURE
that will result in a delay of
the system alarm signal from
the indicated circuits. The
total delay time (control plus
smoke detectors) shall not
exceed 60 seconds. No other
smoke detector shall be
connected to these circuits
unless approved by the local
Authority Having Jurisdiction.
*Zone(s)________________
*where alarm verification is used
Programmed Delay is 60
seconds by default. The
delay is programmable from 5
– 60 seconds.
X1
X2
- Proprietary Service (DACT)
- Auxiliary Service (Local Energy)
The FireNET 4127 has been verified to comply with
FCC Rules Part 15, Class A Operation is subject to the
following conditions:
1. This device may not cause radio interference.
2. This device must accept any interference received,
including any that may cause undesired operation.
F.C.C. registration number: US:HBPAL01BFN-DAC
WARNING
BATTERIES SHOULD BE INSPECTED ANNUALLY & REPLACED EVERY 3-5 YEARS
(DO NOT PARALLEL BATTERIES)
USE ONLY UL RECOGNIZED SEALED LEAD ACID BATTERIES
10K OHM
END-OF-LINE
RESISTOR
(EOLR)
P/N 0400-0104 6
RS485 TO NEXT FireNET PANEL
ON NETWORK (Supervised)
ZERO OHM SHORTING
JUMPERS MUST BE USED
FOR CLASS B OPERATION
P/N 0400-01025
: SLC LOOPS 1 - 4 ARE SUPERVISED
(Supervised)
(Supervised)
RS232 DATA PORT
FOR CONFIGURATION
COMPUTER & SOFTWARE
(Disconnect after use)
Printer
Cable must not exceed 20ft.
(real-time event logging)
RS485
NETWORK
TX/RX
LED’s
ENABLE CONTROLS
KEYSWITCH (not present
on the Denver Door build)
SLC LOOPS
1 - 4
RELAYS
NAC 1-4
Signaling Line Circuit. Out terminals
used for Class B or A wiring.
Fire 1, Trouble , Fire 2, Supervisory,
and Auxiliary condition relay contacts
Notification Appliance Circuits #1-4.
(EOLD PN# 0400-1023 required)
X1 - TOP TERMINAL STRIP ELECTRICAL RATINGS FOR MAIN CONTROL UNIT
32VDC
30VDC
30VDC
30VDC
24VDC
24VDC
400mA
400mA
400mA
400mA
1 A
1 A
1 A
2.5A
2.5A
1, 5, 9, 13
3, 7, 11, 15
4, 8, 12, 16
18, 21, 24, 27, 30
19, 22, 25, 28, 31
32, 34, 36, 38
33, 35, 37, 39
2, 6, 10, 14
17, 20, 23, 26, 29
-OUT
+ OUT
-IN
+ IN
NC
C
NO
+
-
32VDC
32VDC
32VDC
Signaling Line Circuit. In terminals
used for return loop for Class A wiring.
TERMINAL STRIP ELECTRICAL RATINGS FOR THE POWER SUPPLY MODULE
N/A N/ A
TB6
: Style 7 - Refer to Section 5.17.1 in Manual
: SLC Max Impedance is 50 Ohm, 1uF, 1mH
See FireNET Installation Manual as noted below
for SLC branch circuit cable requirments
FireNET employs an option for Sounder Time-
Out (for NAC/SOM/ASB), which can be programmed in 5
min. increments between 5-60 min. Option is disabled by
setting the value to 0 (default condition).
Refer to A. 4 for
Compatible Devices
(Regulated)
Refer to A.4 for
Compatible Devices
(Regulated)
EARTH
GROUND
HOT
12 VOLT Sealed Rechargeable
Battery
60 AH Maximum
12 VOLT Sealed Rechargeable
Battery
60 AH Maximum
POSITIVE
(+)
NEGATIVE
(-)
- +
+ -
NEUTRAL
AC 120VAC INPUT
20 AMP Breaker
Max
(supervised)
EARTH GROUND STUD
Refer to A.3 for Compatible Devices
(Special Application for synchronized and
non-synchronized loads)
10 Amp in-line Fuse (supervised)
Bussman AGC-10 or equiv.
Earth Ground
AC Neutral
120VAC, 50/60Hz 2.1A
G
N
240VAC, 50/60Hz
1.1A
AC Line
120VAC, 50/60Hz
L
240VAC, 50/60Hz 1.1A
2.1A
TB4 +DC Output
+24VDC
0 - 4 Amps
+24VDC
-DC Output
DC Common 0 - 4 Amps
DC RTN
+ Battery
+24VDC
5A Max
- Battery
DC Common 5A Max
TB3
(Supervised)
F2 – 3A, 250VAC, slow
blow, 5 x 20mm fuse
All circuits are inherently Power
Limited except AC/Battery inputs.
All Supervised Circuits are identified.
Battery cables and
jumpers are supplied
with the panel
Hochiki America
EOL Device
(EOLD)
P/N 0400-01023
See for
additional NAC
requirements.
NOTE 1:
(Single Circuit Synchronization)
Synchronized audible notification
appliances connected to one NAC
output are not to be installed within
hearing range of the synchronized
audible notification appliances on
another NAC cirucuit.
Synchronized visual notification
appliances connected to one NAC
output are not to be installed within
line of site of the synchronized visual
notification appliances on another
NAC cirucuit.
For synchronized NAC applications,
the outputs are Special Application
with a compatibility range of 19.3 ~
25.95 VDC.