FireNET 4127 I & O Manual v1.90 UL
9.9.2.2 Setting inputs (Panel I/O and Devices on a Loop)
The input settings window can be accessed by right-clicking on the Navigation tree
input item, and clicking on
Edit Settings...
After making the changes click OK to accept the settings, and exit from the window.
Or click Cancel to cancel all changes and exit from the window.
Options: Fire
Fire inputs activate outputs that are General Alarm mode in accordance with the rules
of General Alarm mode. Control panel outputs will include the following:
Common Fire LEDs
Pulsing Buzzer
NAC Outputs
Fire 1 Contact
Fire 2 Contact
Fire Routing Output
Outputs (if flag set)
LCD Fire Message, Address And Location Text Of Input
Options: Trouble
Trouble inputs activate any output configured as a trouble output. Trouble inputs will be
annunciated by the control panel as follows:
General Trouble LED
Continuous Buzzer
Trouble Contact
Trouble Routing Output
Outputs (if flag set)
LCD Trouble Message, Address And Location Text Of Input
Options: Pre-Alarm
Sensors or inputs can generate a Pre-Alarm. This activates any outputs configured to
respond to a pre-alarm. The control panel will respond as follows to a Pre-Alarm:
Pre-Alarm LED
Continuous Buzzer
Outputs (if flag set)
LCD Pre-Alarm Message, Address And Location Text Of Input
Options: Supervisory Alarm
Input modules, sensors and duct sensors can be configured to create a Supervisory
alarm when activated. A Supervisory alarm will produce the following response by the
panel:
Supervisory Alarm LED
Continuous Buzzer
Supervisory Contact
Outputs (if flag set)
LCD Supervisory Alarm Message, Address And Location Text Of Input