152
FireNET 4127 I & O Manual v1.90 UL
9.9.2.2 Setting inputs (Panel I/O and Devices on a Loop)
The input settings window can be accessed by right-clicking on the Navigation tree
input item, and clicking on
Edit Settings...
After making the changes click OK to accept the settings, and exit from the window.
Or click Cancel to cancel all changes and exit from the window.
Options: Fire
Fire inputs activate outputs that are General Alarm mode in accordance with the rules
of General Alarm mode. Control panel outputs will include the following:
• Common Fire LEDs
• Pulsing Buzzer
• NAC Outputs
• Fire 1 Contact
• Fire 2 Contact
• Fire Routing Output
• Outputs (if flag set)
• LCD Fire Message, Address And Location Text Of Input
Options: Trouble
Trouble inputs activate any output configured as a trouble output. Trouble inputs will be
annunciated by the control panel as follows:
• General Trouble LED
• Continuous Buzzer
• Trouble Contact
• Trouble Routing Output
• Outputs (if flag set)
• LCD Trouble Message, Address And Location Text Of Input
Options: Pre-Alarm
Sensors or inputs can generate a Pre-Alarm. This activates any outputs configured to
respond to a pre-alarm. The control panel will respond as follows to a Pre-Alarm:
• Pre-Alarm LED
• Continuous Buzzer
• Outputs (if flag set)
• LCD Pre-Alarm Message, Address And Location Text Of Input
Options: Supervisory Alarm
Input modules, sensors and duct sensors can be configured to create a Supervisory
alarm when activated. A Supervisory alarm will produce the following response by the
panel:
• Supervisory Alarm LED
• Continuous Buzzer
• Supervisory Contact
• Outputs (if flag set)
• LCD Supervisory Alarm Message, Address And Location Text Of Input