Modbus Communications 36
HP-327 HIT-4U
Register
(Decimal)
Description
Data
Type
Access Notes
32 Request Event
Logs
U16
(2)
FP32
(4)
RO
700 Request Hourly
Logs
FP32
(4)
RO
701 Request Daily
Logs
FP32
(4)
RO
1002 Software
Version
FP32 RO
1003 Device Type U16 RO 0=4U, 1=4G, 2=4L
1005 Turbine Serial
Number
U32 R/W 1 – 99999999
1006 Electronic ID
Number
U32 R/W 1 – 99999999
1007 Password U16 R/W 0000-9999
1008 Lock Unit U16 R/W 0=No, 1=Yes
1009 Slave Address U16 R/W 0-253
1010 Baud Rate U16 R/W 0 = 9600, 1 = 57000,
2 = 115200
1011 Sample Time U16 R/W 1-80
1013 Contract Hour U16 R/W 1-24
1200 Year U16 R/W 0-99
1201 Month U16 R/W 1-12
1202 Day U16 R/W 1-31
1203 Hour U16 R/W 1-24
1204 Minute U16 R/W 0-59
1205 Second U16 R/W 0-59
2000 Total Units U16 R/W 0=gal, 1=bbl, 2=L,
3=lb, 4=kg, 5=acf,
6=acfx1000, 7=scf,
8=scfx1000, 9=m3,
10=nm3