Modbus Communications 40
HP-327 HIT-4U
Register
(Decimal)
Description
Data
Type
Access Notes
7011 Request Current
Total
FP64 R/W 0 – Max limited by
total decimal point
selection:
99999.999,
999999.99,
9999999.9,
99999999.
This register is also
used to clear total by
writing 0 or set total
by writing desired
value.
16-bit registers
available at
address 7052-7055
(FP64) and 7060-
7061 (FP32)
7013 Request
Previous Day
Total
FP64 RO 0 – 99999999
7014 Request
Previous Day
Run Time
Seconds
FP32 RO 0 – 86400
7015 Request
Previous Hour
Total
FP64 RO 0 – 99999999
7016 Request
Previous Hour
Run Time
Seconds
FP32 RO 0 - 3600
7018 Request Hourly
Download
Pointer
FP32 RO -1 (cleared logs) -
767
7019 Request Daily
Download
Pointer
FP32 RO -1 (cleared logs) -
383