To enter the Advanced menu (installer set-up):
Press the menu key for 5 seconds.
English, Francais, Espanol, Deutsch, Nederlands, Italiano
OpenTherm boiler data when a vailable
Min: 5.0°C to 21.0 °C, Max:21.0°C to 37.0 °C
1 = daily schedule, 2 = 5+2 days schedule
Opt.start on
Opt.stop off
Opt start: 0 = off, 1 = on, 2 = Delayed start
Opt stop: 0 = off, 1 = on
Format: 24h
Time: --:--
Date:
01/09/2016
Clock format: 1 = 12h, 2 = 24h
Setup time and date
Bind, check RF and clear bind.
Factory, schedule, Wi-Fi and Homekit reset
Minimum ON time
(in minutes)
Note :
a. To change Cycle/Hour,
b. To change Minimum ON Time,
1. Set Minimum ON Time to 4 minutes.
2. Set Cycle/Hour to 3.
When bound to a 2-channel receiver box the system type can be set: Heating only, Heating
+ Hot Water
If the Receiver box is connected to an OpenTherm appliance various appliance specific data
can be viewed. The data displayed is depending on what the appliance is providing.
The normal lower temperature limit of 5
o
C can be increased up to 21
o
C to protect the
inhabitants from cold conditions. This is a useful feature aimed at supporting the elderly,
children and disabled inhabitants.
The normal upper temperature limit of 35
o
C can be reduced down to 21
o
C to save energy.
This feature is useful for leased homes and apartments.
The thermostat has 2 default schedules: daily (every day) and 5+2 (week + weekend days)