Why is my Honeywell Home Fan HRV/ERV operating only on high speed?
- NNathan HodgesAug 20, 2025
Your Honeywell Home Fan might be operating only on high speed due to several reasons: * The dehumidistat of the wall controls may be activated. In this case, ensure all wall control and Speed Control wire connections correspond to their matching letters. * The T-3 Timer 20/40/60 mins may be activated. Ensure no nails, staples, or screws are shorting out the wires. * There could be a short circuit between the G & R terminals of REMOTES on Speed Control™. In this case, replace the LVC PCB board, wall control, and wires. * A faulty wire between the control and H/ERV. Inspect the wires to ensure no damage. * A faulty wall control. Remove the wall control and verify it at the H/ERV.