Chapter 10 Program Example
11 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB Users Guide R220
Honeywell January 2019
Select the Pnet for module type, position of current master communication module is set the base number
and slot number. Communication cycle is set free from 20ms to 10s (Basic 20ms), It will be a data
transmission cycle between CPU module of PLC and Master communication module. In emergency, output
setting is set suitable to users environment. Click OK and then Block is created below High-speed link 1,
Double click it.
After block is created, click the index of block information frame (right frame). Click [Online]-
[Communication module setting]-[Config. Upload (Dnet, Pnet)] and it brought the setting information in
SyCon.
[Figure 10.1.22] Config. Upload (Dnet, Pnet)
After SyCon setting file is uploaded, setting information is displayed in block window as shown below.
Double click the applicable index to set the address. Set %MW200 for station3, %MW0 for station 4
and %MW3000 for area to read, %MW3011 for area to save of station 6.