Chapter 10 Program Example
43 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User’s Guide R220
Honeywell January 2019
After add P2P communication, set the communication module as follow [Figure 10.4.2]
[Figure 10.4.3] Communication module setting
Register the P2P parameter that defined in P2P block setting window. Pnet I/F module reads 10
bytes of 0x04 slot, 0x15 index from slave module and saves to %MB100 of PLC.
[Figure 10.4.4] P2P READ block setting
[Figure 10.4.5] P2P READ variable setting
After P2P READ setting, set P2P WRITE setting. Read 10 bytes from %MB200 of PLC and save
0x04 slot, 0x15 index of slave.