2.1 General Specifications
General specifications of ML200 series are as specified below in Table 2.1.
No.
Items
Specification
Reference
1
Ambient Temp.
0 ~ 55 C
2
Storage Temp.
25 ~ 70 C
3
Ambient humidity
5 ~ 95%RH (Non-condensing)
4
Storage humidity
5 ~ 95%RH (Non-condensing)
5
Vibration Immunity
Occasional vibration
-
Frequency
Acceleration
Pulse width
Times
IEC61131-2
5≤f< 8.4
-
3.5mm
10 times
each
direction (X,Y
and Z)
8.4≤f≤150
9.8 (1G)
-
Continuous vibration
Frequency
Acceleration
Pulse width
5≤f< 8.4
-
1.75mm
8.4≤f≤150
4.9 (0.5G)
-
6
Shocks Immunity
Peak acceleration : 147 m/s
2
(15G)
Duration : 11ms
Pulse wave type : Half-sine (3 times each direction per each axis)
IEC61131-2
7
Noise Immunity
Square wave
impulse noise
AC : ±1,500V
DC : ±900V
LSIS internal
test spec.
Electrostatic
discharge
Voltage: 4kV (Contact discharge)
IEC6113 1 -2
IEC61000-4-2
Radiated
electromagnetic
field noise
8 0 ~ 1 0 00 MHz, 10V/m
IEC61131-2,
IEC61000-4-3
Fast transient
/Burst noise
Classific
ation
Power
supply
Digital/Analog Input/Output,
Communication Interface
IEC61131-2
IEC61000-4-4
Voltage
2kV
1kV
8
Operation
ambience
Free from corrosive gases and excessive dust
9
Altitude
Less than 2,000m
1 0
Pollution degree
Less than 2
1 1
Cooling method
Air-cooling
Table 2.1 General Specifications
Note
1) IEC (International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic field, publishes international standards and manages applicable estimation system related with.
2) Pollution degree:
An index indicating pollution degree of the operating environment which decides insulation performance of the devices.
For instance, Pollution degree 2 indicates the state generally that only non-conductive pollution occurs. However, this
state contains temporary conduction due to dew produced.