EasyManua.ls Logo

Honeywell 2MLL-PMEC - Communication Example with 2 MLL-PMEC

Honeywell 2MLL-PMEC
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10 Program Example
14 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB Users Guide R220
Honeywell January 2019
10.2 Example of communication with 2MLL-PMEC
This example shows a program that is installed on No. 0 slot of ML200 No. 0 base, sending and
receiving data to Smart I/O module(Station Number 4 and 1) and Extended Smart I/O Pnet(Station
2).
[Figure 10.2.1] I/O Structure and Sending/Receiving Data
Sending/Receiving Structure
Read Area
Save Area
Size (byte)
2MLL-
PMEC
(Master)
MPL-TR2A
Sending
%MW0(2byte)
-
2
MPL-D22A
Receiving
-
%MW200(2byte)
2
MPL-
BSSA
MLE-TN32A
Sending
%MW3000(4byte)
-
Sending(22byte)/
Receiving(20byte)
MLE-DC32A
Receiving
-
%MW3011(4byte)
MLF-AD04A
Receiving
-
%MW3013(8byte)
MLF-DV04A
Sending
%MW3002(8byte)
-
MLF-DC04A
Sending
%MW3006(8byte)
-
MLF-RD04A
Receiving
-
%MW3017(8byte)
MLE-RY16A
Sending
%MW3010(2byte)
-
[Table 10.2.1] High-Speed Link Sending/Receiving Map
In the table above, ML200 CPU sends 2 byte data in %MW0 area to MPL-TR2A and 22 byte data
in %MW3000~3010 area to MPL-BSSA and saves 2 byte (16 points) input data of MPL-D22A
in %MW200 area of ML200 CPU and 20 byte input data of MPL-BSSA in %MW3011~3020 area of
ML200 CPU.
10.2.1 N Configurator settings
To exchange data between the systems as in [Figure 10.2.1], it is convenient for the user to
write high-speed link sending/receiving map. In addition, it is necessary to write high-speed link
parameters after setting Network Configuration through N Configurator and download to PLC in
order to send/receive data as in [Table 10.2.1].

Related product manuals