EasyManua.ls Logo

Honeywell 2MLL-PMEC - Page 143

Honeywell 2MLL-PMEC
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10 Program Example
26 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB Users Guide R220
Honeywell January 2019
After N Configurator setting file is uploaded, setting information is displayed in block window as shown
below. Double click the applicable index to set the address. Set %MW200 for station3, %MW0 for station 4
and %MW3000 for area to read, %MW3011 for area to save of station 6.
[Table 10.2.22] High-speed link block setting
After finish the setting, setting information is downloaded in PLC. Select [Online] [Write] (standard settings,
High-speed link, P2P). Here, Check High-speed link to download and click OK.
[Table 10.2.23] Write
After Write is finished, the operation is by applicable high-speed link enabled. Select the [Online]-
[Communication module setting]-[Enable Link] (High-speed, P2P). And Link Enable window is displayed as
shown below. Select the applicable High-speed link number and then select Write to set.

Related product manuals