Chapter 10 Program Example
38 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB Users Guide R220
Honeywell January 2019
[Figure 10.3.17] Screen of communication module setting
Select the Pnet for module type, position of current master communication module is set the base number
and slot number. Communication cycle is set free from 20ms to 10s (Basic 20ms), It will be a data
transmission cycle between CPU module of PLC and Master communication module. In emergency, output
setting is set suitable to users environment. Click OK and then Block is created below High-speed link 1,
Double click it.
After block is created, click the index of block information frame (right frame). Click [Online]-
[Communication module setting]-[Config. Upload (Dnet, Pnet) and it brought the setting information in N
Configurator