HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
41 66-2069EP—08
flamecount of between 12 and 22, and note the
flamecount.
a. Increase the gain and store the setting. Ensure
the flamecount increased.
b. Decrease the gain and store the setting. Ensure
the flamecount decreased.
5. Restore all original settings as recorded in Setup and
reconnect the signal processor to the safety system.
Product Decommissioning
When required, decommissioning of the S70X and S80X
viewing heads should be performed in accordance with
requirements of the overall safety system.
DISPOSAL
Devices with electronic components:
WEEE Directive 2012/19/EU – Waste Electrical and
Electronic Equipment Directive
At the end of the product life (number of
operating cycles reached), dispose of the
packaging and product in a corresponding
recycling center. Do not dispose of the unit with
the usual domestic refuse. Do not burn the
product.
On request, old units may be returned carriage
paid to the manufacturer in accordance with the
relevant waste legislation requirements.

Other manuals for Honeywell 800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell 800 Series and is the answer not in the manual?

Honeywell 800 Series Specifications

General IconGeneral
BrandHoneywell
Model800 Series
CategoryBarcode Reader
LanguageEnglish

Related product manuals