Installation and Operations Guide
|
Key illustrations
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
13
Figure 9 Communications conne ctions for VLX and EXP/AXM.
MS/TP S upports up to 10
BACne t MS /TP de vice s .
Se e page 32.
AC-2650 to conne ct
compute r for
Hype rTe rminal
configuration or testing.
Se e page 40 and
page 69.
Ethe rne t Cate gory 5 or be tte r drop cable
with RJ-45 jack. Re commended BACne t
network conne ction. Se e page 31.
Pane l g ro und to te rminate s hie lds
and unit ground. S e e page 25.
EXP/AXM
communications
c able 18 AWG two
conductor twis ted-
shield cable. 10 feet
(3.048 m) max.
be twe e n units .
Te rminating
re s is to rs 120 Ohm
matche d pre cis ion
te rminating re s is tors
at each end.
Shie ld Run one e nd to
pane l ground, tape back
at othe r e nd. Tie through
at inte rme diate EXPs /
AXMs .

Related product manuals