EasyManua.ls Logo

Honeywell ALERTON ACM-VLX - Properties of VLX;ACM-VLX BI Objects

Honeywell ALERTON ACM-VLX
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operations Guide
|
ACM-VLX/VLX/EXP/AXM
84
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Properties of VLX/ACM-VLX BI objects
Table 29 Prope rtie s of the VLX/ACM-VLX BI obje ct
Prope rty W Type Example Re marks
de s cription
Characte r s tring Fan S tatus An e ditable de s cription of the obje cts location or
function.
e ve nt-s tate Enumerated NORMAL
obje ct-ide ntifie r BACne t_ Object_
Id e n tifie r
BI 10 This prope rty cons ists of the Obje ct_Type prope rty and
the Object Ins tance , which is a nume ric code that
identifies the object of interest.
obje ct-name
ACM
-VLX
Characte r string EXP 7 BI 10/
AXM 7 BI 10
The Obje ct Name prope rty is writable whe n us ing the
ACM-VLX only and not in the VLX/VLX-Platinum.
obje ct-type Enumerated BI Indicate s a binary input (BI) object.
out-of-s e rvice
Boole an FALS E TRUE de couple s the pres e nt-value prope rty from the
physical input, and the pre s e nt-value doe s not track
furthe r phys ical input change s . While TRUE, the
present-value can be change d to any value to simulate
conditions for te s ting. FALS E indicate s that the pre s e nt-
value is tracking change s to the physical input.
polarity NORMAL
present-value
Logical s tate ACTIVE ACTIVE or INACTIVE. Writable only whe n out-of-s e rvice
= TRUE (s e e he re in).
reliability NO FAULT
DETECTED
Othe r possibility is UNRELIABLE_OTHER.
status -flags Bit s tring In alarm = 0,
fault = 0,
ove rridden =
0, out of
se rvice = 0
A four-pos ition bit s tring that indicate s the status of the
obje ct. If a s tatus bit =1, that status is TRUE.
active-text
ACM
-VLX
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
inactive -te xt
ACM
-VLX
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
change -of-state -time ACM-VLX: indicate s the las t time it change d s tate (OFF
to ON or ON to OFF).
change -of-state -count ACM-VLX: indicate s the las t time it change d s tate (OFF
to ON or ON to OFF).
time -of-s tate -count-
re s e t
ACM
-VLX
Turn ON to re s e t the change-of-s tate count. Will
automatically change back to OFF.
e lapsed-active-time Runtime in s e conds
time -of-active -time -
re s e t
Turn ON to re s e t the e laps e d-active -time prope rty. Will
automatically change back to OFF.