Properties of VLX/ACM-VLX BV objects
Table 31 Prope rtie s of VLX/ACM-VLX BV objects
Prope rty W Type Example Re marks
active-te xt ON
de s cription
Characte r string Occupie d
Setpoint
A de s cription as s igne d for the obje ct’s function.
e ve nt-s tate Enumerated NORMAL
inactive -te xt OFF
obje ct-ide ntifie r BACne t_ Object_
Id e n tifie r
BV 8413 This prope rty cons ists of the object-type property and the
obje ct instance , which is a nume ric code that ide ntifie s
the object of interest.
obje ct-name
ACM
-VLX
Characte r string BV 8413
obje ct-type Enumerated BV Indicate s a binary value (BV).
out-of-s e rvice Boole an FALS E
present-value
Enumerated INACTIVE Eithe r ACTIVE (ON) or INACTIVE (OFF).
status -flags Bit s tring In alarm = 0,
fault = 0,
ove rridden =
0, out of
se rvice = 0
A four-pos ition bit s tring that indicate s the status of the
obje ct. If a s tatus bit =1, that status is TRUE.
priority-array BACne t
PriorityArray
<Array of
BACne t
P rio rityVa lue >
An array of prioritize d value s (indexe s 1-16) controlling
the present-value , inde x 1 having the highe s t priority.
The value with the highest priority controls the pre se nt-
value . Poss ible values for priority-array inde xe s are
ACTIVE, INACTIVE, or NULL. A NULL value indicate s
no command is iss ue d at that priority-array inde x.
relinquis h-de fault
REAL 0 De fault value to be us e d for pre s e nt-value prope rty when
all priority-array inde xe s are NULL.
active-text
ACM
-VLX
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
inactive -te xt
ACM
-VLX
Prope rty is writable whe n us ing the ACM-VLX only and
not in the VLX/VLX-Platinum.
change-of-state-time
ACM
-VLX
ACM-VLX: indicate s the las t time it change d s tate (OFF
to ON or ON to OFF).