Installation
Mount devices in a position that allows clearance for wiring, servicing, removal, and terminal block connection.
The VIP controller and VXIO modules may be mounted in any orientation.
IMPORTANT Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of
the device, or in areas where escaping gas or other explosive vapors are present.
Power
The VIP controller and expansion modules require a 24 VAC [20 VAC (min), 30 VAC (max)], 50/60 Hz, half-wave
power from a UL Listed Class 2, 24 VAC transformer.
WARNING! Half-wave devices and full-wave devices must not use the same AC transformer. Maintain wiring polarity.
Fig. 1 Use separate transformers for controllers and load power.
Power Consumption
Total power consumption must be based on the sum of the VA rating for each controller and I/O expansion module. The
total must not exceed 100 VA. Figures 1 and 3 represent options for powering the I/O expansion modules separate
from the VIP-363-HOA controller.
Part
VA Minimum
Load
(No BO Load)
VA Maximum
Load
BO Load
(HOT A)
BO Load
(HOT B)
BO 24 VAC
Load Max
VIP-363-VAV 15 VA 100 VA 100 VA 72 VA 1.5 A
VIP-363-HOA 15 VA 100 VA 100 VA 72 VA 1.5 A
VXIO-322 6 VA 87 VA 72 VA 72 VA 1.5 A
VXIO-965 3 VA 100 VA 100 VA 72 VA 1.5 A