LYNX LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
EN0Z-0957GE51 R0615
11
Typical controller wiring for PWM reheat and PWM
peripheral heat valve actuator (see Fig. 17).
Typical controller wiring for AHU application (see Fig. 18).
Typical controller wiring for 4…20 mA enthalpy sensors
and digital inputs (see Fig. 19).
Typical controller wiring for 4…20 mA heating, cooling,
and model ML6161 floating motor control (see Fig. 20).
Typical controller wiring for a pneumatic transducer, model
RP7517B (see Fig. 21).
12
3
4
567890
12
3
4
567890
2222222222
333333333
4
1234
5
678 1
11111111121
234
5
6789009
CLLYVL6438NS
24 VAC
24 VAC COM
E GND
SHLD
SBUS1
SBUS2
NET-1
NET-2
DO-1
DO-2
COM
COM
COM
COM
DO-3
DO-4
DO-5
DO-6
DO-7
DO-8
AO-1
AO-2
AO-3
DI-1
DI-2
DI-3
DI-4
20VDC
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
COM
COM
COM
COM
COM
COM
1
24VAC
24VAC COM
LonWorks Bus
LonWorks Bus
CLCM4T111
WALL MODULE
GND
SENSOR
SET-POINT
BYPASS
LED
5
6
7
4
3
2
1
AIR FLOW
PICK-UP
C770A AIR
TEMP. SENSOR
REHEAT STAGE 3
REHEAT STAGE 2 (OR CLOSE)
REHEAT STAGE 1 (OR OPEN)
DAMPER CLOSE
DAMPER OPEN
SERIES OR PARALLEL
FAN CONTACTOR
REHEAT STAGE
CONTACTORS
ML6161
DAMPER
CTUATOR
CCW
COM
CW
WINDOW CONTACTS
(CONTACTS CLOSED
= WINDOW CLOSED)
OCCUPANCY SENSOR
(CONTACTS CLOSED
= OCCUPIED)
2
Fig. 15. Controller wiring diagram (CLLYVL6438NS
shown) for typical VAV application
NOTE 1: Earth ground wire length should be held to a
minimum. Use the heaviest gauge wire available,
up to 14 AWG (2.0 mm
2
), with a minimum of 18
AWG (1.0 mm
2
), for earth ground wire.
NOTE 2: Contacts must be suitable for dry switching, 5 V at
10 mA. Use sealed type, gold-flashed, or pimpled
contacts.
12
3
4
567890
12
3
4
567890
2222222222
333333333
4
12
3
4
5678
1
11111111121
2
3
4
56789009
CLLYVL6436AS
24 VAC
24 VAC COM
E GND
SHLD
SBUS1
SBUS2
NET-1
NET-2
DO-1
DO-2
COM
COM
COM
DO-3
DO-4
DO-5
DO-6
AO-1
AO-2
AO-3
DI-1
DI-2
DI-3
DI-4
20VDC
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
COM
COM
COM
COM
COM
COM
STAGE 3
STAGE 2
STAGE 1
AIR FLOW
PICK-UP
CLCM4T111
WALL MODULE
GND
SENSOR
SET-POINT
BYPASS
LED
5
6
7
4
3
2
1
WINDOW CONTACTS
(CONTACTS CLOSED
= WINDOW CLOSED)
OCCUPANCY SENSOR
(CONTACTS CLOSED
= OCCUPIED)
2
C770A AIR
TEMP. SENSOR
1
24VAC
24VAC COM
LonWorks Bus
LonWorks Bus
Fig. 16. Controller wiring diagram (CLLYVL6436AS
shown) for typical VAV application with staged reheat
NOTE 1: Earth ground wire length should be held to a
minimum. Use the heaviest gauge wire available,
up to 14 AWG (2.0 mm
2
), with a minimum of 18
AWG (1.0 mm
2
), for earth ground wire.
NOTE 2: Contacts must be suitable for dry switching, 5 V at
10 mA. Use sealed type, gold-flashed, or pimpled
contacts.