Design of temporary edge protection
EN 13374 sets the following requirements for
Classes A, B, and C, edge protection:
Edge protection must be at least 1.0 m high,
measured perpendicular to the working sur-
face.
Principal (top) and intermediate guardrails or
other means of intermediate protection must
be provided.
A toeboard, if provided, must have a height of
at least 150 mm with a maximum gap of 20
mm from the lowest part of the toeboard to the
working surface.
Safety nets used as edge protection must con-
form to EN 1263-1.
Class A design
The edge protection may not deviate
from the vertical line A by more than
15°.
The edge protection openings may not
be more than 470 mm in one direction,
when intermediate guardrails are used.
The edge protection openings may not
be more than 250 mm in one direction,
when there is no intermediate guard-
rail.
Class B design
The edge protection may not deviate from the
vertical by more than 15° outwards or inwards.
The edge protection openings may not be more
than 250 mm in one direction.