EasyManua.ls Logo

Honeywell D355PL User Manual

Honeywell D355PL
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
FL-300-000 1 I56-3255-003R
D355PL Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
NOTE: The D355PL come with the sensor head factory installed, part number SD355R.
Table of Contents Page
[1] Limitations of Duct Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . .1
[2] General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
[3] Contents of the Duct Smoke Detector Kit . . . . . . . . . . . . . . . . . . . . . .1
[4] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
[5] Sampling Tube Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
[6] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
[7] Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
[9] Dectector Cleaning Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[10] Sensor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
[11] Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
BEFORE INSTALLING
Read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Appli-
cations (A05-1004), which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies of this manual
are available online at www.systemsensor.com. NFPA Standards 72 and 90A
should also be referenced for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 requirements. The detector should be cleaned at least once a year.
[1]LIMITATIONS OF DUCT SMOKE DETECTORS
WARNING
The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR
PROTECTION as a means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user
read NFPA Standards 90A, 72, and 101. The D355PL Air Duct Smoke Detectors
are listed per UL 268A.
This device will not operate without electrical power. Fire situations may
cause an interruption of power. The system safeguards should be discussed
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within
ALL electrical and environmental specifications listed in this manual and the
sensor head installation manual. Failure to comply with these requirements
may prevent the detector from activating when smoke is present in the air duct.
[2]GENERAL DESCRIPTION
Smoke introduced into this air duct system will be distributed throughout the
entire building. Smoke detectors designed for use in air duct systems are used
to sense the presence of smoke in the duct.
Model D355PL Air Duct Smoke Detector utilizes photoelectric technology for
the detection of smoke. This detection method, when combined with an ef-
ficient housing design, samples air passing through the duct and allows detec-
tion of a developing hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated at the fire control panel monitoring the detector,
and appropriate action can be taken to shut off fans, blowers, change over air
handling systems, etc. These actions can facilitate the management of toxic
smoke and fire gases throughout the areas served by the duct system.
The D355PL incorporates a sensor cover tamper feature that provides a trou-
ble signal at the panel immediately if the cover is removed or improperly in-
stalled. Proper installation of the sensor cover removes the trouble condition.
If programmed with the system control panel, two LEDs on each duct smoke
detector light to provide local visible indication.
The D355PL provides a remote alarm output for use with auxiliary devices,
such as the RA400Z/RA100Z remote LED annunciator, as well as remote test ca-
pability with the RTS451/151 or RTS451KEY/RTS151KEY Remote Test Stations.
[2.1] DETECTOR FEATURE SET
– Utilizes plug-in head, part number SD355R
– Sampling tubes install from front and rear
– Compatible with existing accessories
– Able to address detector per code switches on sensor head.
[3]CONTENTS OF THE DUCT SMOKE DETECTOR KIT
1. Sensor/power board assembly and covers sensor head is factory installed
2. Three #10 sheet metal screws for mounting
3. One test magnet
4. Drilling template
5. One sampling tube end cap
6. One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must
be the correct length for the width of the duct where it will be installed. See
Table 1 on page 3 to determine the inlet tube required for different duct widths.
[4]DETECTOR INSTALLATION
[4.1]VERIFY DUCT AIR FLOW DIRECTION AND VELOCITY
Model D355PL detectors are designed to be used in air handling systems hav-
ing air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to
12 feet can be accommodated. Be sure to check engineering specifications to
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.
[4.2]DETERMINE MOUNTING LOCATION AND CONFIGURATION
On ducts wider than 18 inches it is recommended that the detector be
mounted downstream of a bend, obstruction in the duct, or the supply or
return air inlet.
I56-3255-003R
SPECIFICATIONS
Operating Temperature: –4° to 158°F (–20° to 70°C)
32° to 120°F (0° to 49°C) with module installed in the D355PL
Storage Temperature: –22° to 158°F (–30° to 70°C)
Humidity: 0% to 93% Relative Humidity Non-condensing
Air Velocity: 100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
Rectangular Footprint Dimensions: 14.38 in L×5 in W×2.5 in D (37 cm L×12.7 cm W×6.36 cm D)
Square Footprint Dimensions: 7.75 in L×9 in W×2.5 in D (19.7 cm L×22.9 cm W×6.35 cm D)
Weight: 1.8 pounds; 0.82 kg
Operating Voltage Range: 15 to 32 VDC
Standby Current: 300µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)
Max. Alarm Current (LED on): 6.5 mA @ 24 VDC
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE STANDBY ALARM
RA400Z/RA100Z 0mA 12mA Max.
RTS451/RTS151 0mA 12mA Max.
RTS451KEY/
RTS151KEY
12mA 12mA Max.
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
Question and Answer IconNeed help?

Do you have a question about the Honeywell D355PL and is the answer not in the manual?

Honeywell D355PL Specifications

General IconGeneral
TypePhotoelectric Smoke Alarm
Alarm Volume85 dB at 10 feet
Test/Silence ButtonYes
InstallationCeiling or Wall Mount
Hush FeatureYes
LED IndicatorYes
Alarm Sound Level85dB
Operating Temperature40°F to 100°F
Humidity Range10% to 95% relative humidity

Summary

Limitations of Duct Smoke Detectors

General Description

Detector Feature Set

Details the key features of the D355PL duct smoke detector, including its plug-in head and compatibility with accessories.

Contents of the Duct Smoke Detector Kit

Detector Installation

Verify Duct Air Flow Direction and Velocity

Ensures the detector is installed in air systems with velocities between 100 to 4000 ft./min. for proper sampling.

Determine Mounting Location and Configuration

Guidance on selecting the optimal placement and orientation for the detector within the duct system.

Drill the Mounting Holes

Instructions for drilling holes in the duct based on the chosen mounting configuration (rectangular or square).

Secure the Duct Detector to the Duct

Steps for securely attaching the detector housing to the duct using provided screws.

Sampling Tube Installation

Sampling Tube Selection

Guidance on selecting the correct sampling tube length for different duct widths for optimal performance.

Sampling Tube Installation Procedure

Detailed steps for installing the sampling tube, including orientation and potential support requirements.

Modifications of Sampling Tubes

Instructions for modifying sampling tubes if duct widths do not match standard recommendations.

Remote Sampling Tube Installation

Describes methods for remote mounting of sampling and exhaust tubes and verifying pressure differentials.

Measurement Tests

Air Flow Test

Procedures to measure differential pressure between sampling and exhaust ports to verify adequate air flow.

Low Flow Air Flow Test Using Dwyer Series 607

Specific test method for verifying air flow in low-velocity systems using a differential pressure transmitter.

Field Wiring and Installation Guidelines

Wiring Instructions

Provides system wiring diagrams and instructions for connecting the D355PL detector.

Set the Address

Instructions on setting the detector's address using rotary switches on the sensor head.

Verification of Operation

Install the Cover

Ensures the detector cover is properly installed for correct operation and tamper detection.

Power the Unit

Guidance on activating the communication line to power up the detector.

Detector Check

Describes expected LED behavior for standby and trouble conditions.

Duct Smoke Detector Test & Maintenance Procedures

Overview of testing and maintenance recommendations, including specific test methods.

Detector Cleaning Procedures

Detector Sensor Cleaning

Step-by-step instructions for cleaning the sensor head, including vacuuming and using compressed air.

Reinstallation

Process for reinstalling the detector after cleaning and restoring system power.

Sensor Replacement

Optional Accessories

Remote Alarm LED Option

Wiring instructions for connecting remote alarm LED annunciators like RA400Z/RA100Z.

Remote Test Using Sensor with Remote Test Capability

Method for remote testing using compatible sensors without requiring a test coil.

Remote Test Using a Test Coil

Procedure for connecting a test coil and remote test station for testing detector functionality.

Additional Module Option

Guidance on installing compatible relay or control modules within the detector housing.

Related product manuals