DISTRIBUTED I/O
EN0B-0090 12
Table 10. LONMARK Object NVs for the XFL524B.
NV Name Type Range Description
nviValue SNVT_switch Receives the value for the output channel.
nvoFeedback SNVT_switch Transmits the feedback value of the Actuator Object. If
the manual override switch is set to auto, or if the
manual override module is not plugged in, the
feedback output reflects the value of nviValue. As
soon as the manual override switch is set to either
manual position, the Actuator Object adopts this
manual value. In this case, the nvoFeedback state
field will be 0xFF (invalid) and the value field will
contain the actuator position.
If the manual override switch is in the automatic posi-
tion, data is transmitted whenever nviValue is written.
If the manual override switch is in the manual position,
data is transmitted whenever the manual position is
changed.
nvoManCnt SNVT_count 0 to 65535 Transmits the number of manual switching operations.
Each transition from the state auto/manual on/manual
off to any other statue is counted by incrementing this
NV.
nvoDiagnose SNVT_count 0 to 65535 Counts the number of times the internal filter for
smoothing the signal from the manual override switch
board has been active.
UCPTSensorConfig 0 = not used
1 = binary (default)
Specifies whether an Actuator Object is processed or
not. If set to 0, the value is not updated.