DISTRIBUTED I/O
EN0B-0090 14
Manual Override Module XFR522A for XFL522B (Analog Output)
Mounts on top of the XFL522B module
Potentiometer settings
automatic or variable 0 – 100%
XFL 522 LEDs remain visible
Dimensions (WxLxH): 47x97x20 mm
Feedback signal including point name, status (manual,
auto), and point value provided to CPU
The XFR522A manual override module mounts directly on
top of the XFL522B. Eight potentiometers on top of the
module can be used to independently vary the output of each
channel from 0 to 100%. Each potentiometer also has an
automatic setting which causes the channel to operate
normally. The LEDs of the XFL522B are also visible.
The manual override module works even if the CPU
XC5010C or XCL5010 is not working.
An optional label is available showing the functional
description generated by CARE.
Manual Override Module XFR524A for XFL524 (Digital Output)
Mounts on top of the XFL524B module
Switch settings:
automatic, off (0) and on (1)
XFL524B LEDs remain visible
Dimensions (WxLxH): 47x97x20 mm
Feedback signal including point name, status (manual,
auto), and point value provided to CPU
The XFR524A manual override module mounts directly on
top of the XFL524B. Six switches on top of the module can
be used to independently switch each of the digital outputs
OFF (0) or ON (1). Each switch also has an automatic setting
which causes the channel to operate normally. The LEDs of
the XFL524B are also visible.
The manual override module works even if the CPU
XC5010C or XCL5010 is not working.
An optional label is available showing the functional des-
cription generated by CARE.
LONWORKS Connector Module XSL511
LONWORKS network connection to CPU
24 Vac voltage supply for distribution to connected
modules
Electronic fuse for 24 Vac
Connection to Distributed I/O modules via sliding bus
connector (L
ONWORKS bus and voltage supply for ten
Distributed I/O modules)
Bus data: speed: 78 Kbaud; length: depending on cable
type, e.g. 1,200 m, free topology 500 m, node-to-node 300
m
The XSL511 L
ONWORKS connector module provides ter-
minals for connecting to the L
ONWORKS bus wiring, as well as
terminals for the 24 Vac supply voltage for the other
modules. The part number for the L
ONWORKS bus termination
module is 209541B.