43-TV-33-81 iss.2 GLO Aug 19 UK 1
eZtrend GR and X Series QXe recorders -
Installation Instruction
Expansion Board
QXe Recorder eZtrend Recorder
This Installation Instruction sheet is intended as a guide for replacing or installing hardware and for setting up
functionality in the recorder. Refer to the User manual for detailed operational requirements.
The eZtrend Gr and QXe recorders are designed for ease of assembly with minimal disturbance to the rest of the unit. If
unsure, please return the unit to your supplier for repair or upgrade.
Removing the case and opening the back of the recorder should only be performed under the following circumstances:
When an item of hardware requires individual replacement.
When an item of hardware is to be retrospectively fitted.
In all other instances it is recommended that the complete unit be returned to an authorised agent or service centre.
For Agency Approved recorders the product needs to be upgraded or repaired by an Authorized Repair facility.
WARNING
HAZARDOUS VOLTAGES
Disconnect all power to the recorder before removing the case and attempting any maintenance procedures.
SAFETY TESTS
Upon completion of service procedures detailed in this manual two basic safety tests should be performed in order to
ensure continued safe operation of the instrument.
Earth Resistance; 25 VDC applied between case and protective earth, bonding resistance should be < 0.1 Ohm.
Insulation Resistance; 500Vdc applied between the earth terminal, and the live and neutral terminal shorted together,
insulation resistance to be >2.0 MOhm. (Mega Ohm, NOT milli Ohm)
Failure to comply with these instructions could result in death or serious injury
CAUTION
OBSERVE ANTI-STATIC PRECAUTIONS
Refer to BS EN61340-5-1: 2001. Basic specification. Protection of electrostatic sensitive devices.
Full anti-static precautions MUST be observed when in contact with the electronics of your recorder.
SAVE DATA, SETUPS AND LAYOUTS
Removal of PCBs and battery back-up will result in the loss of all non-volatile data.
Ensure all data and set-ups are saved.
Failure to comply with these instructions may result in product damage.
Question and Answer IconNeed help?

Do you have a question about the Honeywell eZtrend GR Series and is the answer not in the manual?

Honeywell eZtrend GR Series Specifications

General IconGeneral
TypePaperless Recorder
Input ChannelsUp to 12
Power Supply100-240 VAC, 50/60 Hz
WeightApprox. 1.5 kg (3.3 lbs)
Input TypesThermocouple, RTD, V
Data StorageInternal memory
CommunicationEthernet, RS-485
Operating Temperature0 to 50 °C (32 to 122 °F)
Dimensions144 x 144 mm
Measurement ParametersTemperature, Pressure, Flow, Level
Display5.7 inch TFT color display
Storage Temperature-20°C to 60°C (-4°F to 140°F)

Summary

Recorder Preparation and Safety

General Installation Guidance

Intended as a guide for replacing or installing hardware and setting up functionality in the recorder.

Critical Safety Protocols

Covers hazardous voltages, safety tests, anti-static precautions, and data saving before maintenance.

Case Removal and Panel Mounting

Panel Mounting Procedure

Steps to remove the recorder from its panel for maintenance or upgrades.

Removing the Recorder Case

Instructions for removing the case and back panel assembly for access.

Expansion Board Servicing

Removing the Expansion Board

Procedure to disconnect power, loosen I/O boards, and remove the Expansion Board.

Refitting the Expansion Board

Reverse steps to refit the Expansion Board, ensuring proper connection to the processor board.

Finalizing Expansion Board Installation

Inserting the Expansion Board

Guide for inserting the new or replacement Expansion Board into board guides.

Securing the Recorder Case

Steps to slide the case back, align rear connectors, and refit case screws.