EasyManua.ls Logo

Honeywell HM700A1000 - User Manual

Honeywell HM700A1000
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
QUICK START GUIDE
33-00162-01
HM700A1000
ELECTRODE STEAM HUMIDIFIER
MOUNTING
Mounting Procedure
1. The HM700 humidifier is wall mounted using a key-
hole located on the back of the humidifier.
2. Use #8 x 2 in. (5 cm) screws mounted into 2x4
studs or better if there is drywall or other spacers.
Two screws are needed, one for hanging the unit
and one for securing it so it will not lift off the
keyhole.
3. Install the top screw so that 1/4 in. (6 mm) is
exposed. Raise the unit and place the screw head
through the keyhole.
4. Make sure the unit is level and then insert and
tighten the second screw through the bottom hole.
Tighten the top screw.
Mounting Requirements
Honeywell does not accept responsibility for installation
code violations.
1. Install as close as possible to the steam distributor.
2. Minimize the use of turn or bends in the steam line
as much as feasibly possible.
3. Mount on a suitable wall or vertical surface. Do not
sit the on the floor, where freezing can occur, or on
vibrating surfaces.
4. Allow clearances for plumbing and electrical con-
nections. Consult local and national codes prior to
final location and installation.
5. Install only in areas with ambient temperature
41-104 °F (5-40 °C), and relative humidity 5-95 %
(noncondensing).
6. When possible, mount the HM700 humidifier at a
height convenient for servicing.
Fig. 1. Mounting.
36 in. (92 cm)
duct model
min. front clearance
24 in.(61 cm)
min. height
Mount humidifier
level
As close as
possible to steam
distributor
5-95%

Other manuals for Honeywell HM700A1000

Question and Answer IconNeed help?

Do you have a question about the Honeywell HM700A1000 and is the answer not in the manual?

Honeywell HM700A1000 Specifications

General IconGeneral
Capacity17 Gallons Per Day
Voltage120V
Coverage AreaUp to 4, 200 sq ft
TypeBypass
InstallationInstalled on the return air duct
Water PanelReplaceable water panel
MountingHorizontal or vertical
Output17 gallons per day

Summary

MOUNTING

Mounting Procedure

Step-by-step guide for physically attaching the humidifier to a wall.

Mounting Requirements

Conditions and clearances needed for safe and effective humidifier mounting.

PLUMBING

Water Supply Requirements

Specifications for water quality and connections to the humidifier's water inlet.

Drain Line Requirements

Guidelines for installing the drain line to ensure proper water removal.

ELECTRICAL

Installation Steps

Procedures for connecting electrical power to the humidifier.

STEAM DISTRIBUTION

Install Requirements

Instructions for steam line installation, material, and length.

MAIN RULES FOR ATMOSPHERIC STEAM LINES

Key principles for installing steam lines to prevent issues like back pressure.

INSTALLATION CHECK

Related product manuals