40 HPFF8(E)/HPFF8CM(E) NAC Expander — P/N 53499:B4 10/1/2018
Applications Connecting Multiple Units
Notes for Figures 5.5–5.10:
1. The FACP’s NAC output must be regulated (not Full Wave Rectified [FWR]) if the HPFF8 is programmed for Sync Generator.
2. The number of possible units that can be interconnected depends on the current capability of the FACP output. Each HPFF8 input
draws 12.26 mA at 24 VDC.
3. The total line impedance for interconnected units cannot be such that it creates a voltage drop > 2 VDC.
Zline total =2V/(1 Unit + 1 ELR)
Example: Zline total = 2V/(12.26 mA + (24-2)/4.7K) =118.1 ohms
Figure 5.9 Split Alarm Connections Figure 5.10 Selective Silencing Connections
TB3
REF+ REF– + IN – IN
+ OUT
– IN
+ OUT+ OUT
+ IN
– OUT
SIGNAL 1
SIGNAL 2
TB3
REF+ REF– + IN – IN
+ OUT
– IN
+ OUT+ OUT
+ IN
– OUT
SIGNAL 1
SIGNAL 2
TB3
REF+ REF– + IN – IN
+ OUT
– IN
+ OUT+ OUT
+ IN
– OUT
SIGNAL 1
SIGNAL 2
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
In from FACP
or previous FF8
Out to next
FF8 or return
to FACP
In from FACP
or previous FF8
Out to next
FF8 or return
to FACP
In from FACP
or previous FF8
In from FACP
or previous FF8
Out to next
FF8 or return
to FACP
Out to next
FF8 or return
to FACP
Figure 5.8 Class A Input Connections
ff8connex-ainput.wmf
TB3
TB4TB1
TB2
SW2
LEDs
REF+ REF– + IN IN
+ OUT
– IN
+ OUT+ OUT
+ IN
– OUT
SIGNAL 1 SIGNAL 2
BATT+ BATT–
A+
N/O
N/C COMM
N/O
N/C COMM
AC FAIL
TROUBLE
J1
J2
1L1 1L2 2L1 2L2 3L1 3L2 4L1 4L2A–
conventional
NAC Outputs
to NACs
ELRs or to
next units
FACP
HPFF8 Sync
Generator
(paired outputs
in any
combination of
temporal or a
sync protocol)
NAC Outputs
ELRs or to
next units
TB3
TB4TB1
TB2
SW2
LEDs
REF+ REF– + IN – IN + OUT – IN + OUT+ OUT + IN – OUT
SIGNAL 1
SIGNAL 2
BATT+ BATT–
A+
N/O
N/C COMM
N/O
N/C COMM
AC FAIL
TROUBLE
J1
J2
1L1 1L2 2L1 2L2 3 L1 3L2 4L1 4L2A–
conventional
FACP
NAC Outputs
silenceable
silenceable
HPFF8
Pass-Through
(Slave)
(filtered if
FWR input)
NAC Outputs
to NACs
ELRs or to
next units
ELRs or to
next units
silenced
pair
silenced
pair

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HPFF8 and is the answer not in the manual?

Honeywell HPFF8 Specifications

General IconGeneral
BrandHoneywell
ModelHPFF8
CategoryExtender
LanguageEnglish

Related product manuals