Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 19
Programming Programming
VeriFire Tools: Leave the Display and Control Center box unchecked
in the NFS2-640 and NFS-320/SYS service.
3.3.2 Mass Notification Control Settings for the DVC
Open the General Settings branch of the DVC System Programming Service in VeriFire Tools.
In the General Settings 3 column, set the MN Mode to LOC, ACU, or CCS. The Associated Node Number becomes available in the
Mass Notification Control Settings section.
Enter the node number of the NCA-2 or NFS2-3030 that is associated with the DVC. VeriFire Tools will set this to 0 (zero) if the DVC is
acting as a subsidiary device (i.e., it is not part of an ACU, LOC or CCS).
3.3.3 Set the Priority
NFS2-3030/NCA-2
This field allows the programmer to define the panel’s relative fire and MN priority. The priority may be set at the panel (See Figure 3.6)
or in VeriFire Tools. (See Figure 3.7).
Leave
unchecked.
NFS2-640/NFS-320/SYS General Settings
Branch, “General Settings 2” column
Figure 3.4 VeriFire Tools, NFS2-640/NFS-320/SYS
Enter node # of associated NCA-2 or NFS2-3030. If the DVC is acting as a
subsidiary device, 0 (zero) will be entered automatically.
DVC General Settings Branch,
“General Settings 2” and “General Settings 3” columns
Figure 3.5 DVC MN Mode Setting
NOTE: Program all panels, DVCs, network annunciators and workstations in a system with the same priority settings. The established
priorities must be consistent throughout a system.
DVC will use the priority of the node with which it is associated.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-3030 FACP and is the answer not in the manual?

Honeywell Notifier NFS2-3030 FACP Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-3030 FACP
CategorySecurity System
LanguageEnglish

Related product manuals