SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012 91
Master Programming Level Programming
Note that the following information must be entered for both the Primary and Secondary Central
Station Phone Numbers.
Test Time Interval
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be dis-
played:
The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24
hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens
shown above.
CENTRAL STATION #
1=TEST TIME INT 24
2=ACCOUNT CODE 0000
3=24HR T TIME 0000
Primary/Secondary Screen #1
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
CENTRAL STATION
1=COMM FORMAT
ADEMCO CONTACT ID
2=EVENT CODES
Primary/Secondary Screen #3
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SFP-10UD Series and is the answer not in the manual?

Honeywell NOTIFIER SFP-10UD Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SFP-10UD Series
CategoryControl Panel
LanguageEnglish

Related product manuals