PRO TH4110B Programmable Thermostat
11
In case of difficulty
If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.
Display is blank Make sure fresh AA alkaline batteries are correctly installed (see page 7).
Fan does not
turn on in a
call for heat
Make sure the Fan Operation switch is set to the proper system (see page 6).
Heating system
does not respond
(“Heat On”
appears on
screen)
Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
Check for 24 Vac between the heat terminal (W) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
Check for loose or broken wires between the thermostat and the heating
equipment.
Cooling system
does not respond
(“Cool On”
appears on
screen)
Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
Check for loose or broken wires between the thermostat and the cooling
equipment.
Temperature
settings do not
change
Make sure heating and cooling temperatures are set to acceptable ranges:
Heat: 40° to 90°F (4.5° to 32°C).
Cool: 50° to 99°F (10° to 37°C).
“Cool On” or
“Heat On”
is flashing
Compressor protection timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage to the compressor.
“Heat On” is
not displayed
Set the System switch to Heat
, and set the temperature level above the
current room temperature (see page 10).
“Cool On” is
not displayed
Set the System switch to Cool
, and set the temperature level below the
current room temperature (see page 10).