PRO-2200 Intelligent Controller PRO22IC 9Installation Guide
Description
The Intelligent Controller is the heart of the PRO-2200 and provides the real time
processing for the connected I/O interfaces. It holds the database for the subsystem
configuration and card holders, and the event log buffer in battery-backed memory.
Port 1 provides the standard connection to the host computer.
1. Port 1 may be set up as an RS-232 interface or an RS-485 interface. An optional
interface board (PRO22EN) converts the RS-232 output of port 1 into an Ethernet port
capable of supporting TCP/IP. If this interface board is present, this port must be set
up as an RS-232 interface and Jumper J-14 must be removed.
2. Ports 2 & 3 are RS-485 interfaces.
An on-board real time clock maintains the date and time, taking into account leap year
and accounting for global time zones and daylight savings time changes. The program is
stored in FLASH memory and may be downloaded through a serial port, allowing the
program to be changed without physically changing board components.
Set Up
The controller hardware is configured with jumpers and a set of eight switches. These
jumpers/switches setup the memory chip size, port interface, end of line termination,
controller address, and baud rate. Please refer to the tables.
Jumper Settings:
SREPMUJTATESDETCELES
6,5,4J
3-2 232-SRSI1TROP
2-1584-SRSI1TROP
41J
FFO ORCIMXOBOC,TENREHTESI1TROP
NO584-SRRO232-SRSI1TROP
9J
FFO NOTONSIROTANIMRETLOE584-SR1TROP
NONOSIROTANIMRETLOE584-SR1TROP
21J
FFO NOTONSIROTANIMRETLOE584-SR2TROP
NONOSIROTANIMRETLOE584-SR2TROP
31J
FFO NOTONSIROTANIMRETLOE584-SR3TROP
NONOSIROTANIMRETLOE584-SR3TROP